Binary Input / Binary Input Change Point List - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

8 DNP COMMUNICATIONS
POINT LIST FOR: BINARY INPUT (OBJECT 01) / BINARY INPUT CHANGE (OBJECT 02)
INDEX
DESCRIPTION
0
Alarm condition(s) active
1
Clock not set
2
Clock drifting
3
Internal error: ADC reference out of range
4
Internal error: HC705 processor not responding
5
Internal error: switch input circuit fault
6
PQM (display) option installed
7
T20 (4-20 mA transducer) option installed
8
T1 (0-1 mA transducer) option installed
9
C (control) option installed
10
A (power analysis) option installed
11
Switch A closed
12
Switch B closed
13
Switch C closed
14
Switch D closed
15
Alarm relay energized
16
Auxiliary relay 1 energized
17
Auxiliary relay 2 energized
18
Auxiliary relay 3 energized
19
Aux 1 relay LED active
20
Aux 2 relay LED active
21
Aux 3 relay LED active
22
Alarm LED active
23
Program LED active
24
Simulation LED active
25
Alarm relay LED active
26
Self test LED active
27
Aux 1 relay LED solid (not flashing)
28
Aux 2 relay LED solid (not flashing)
29
Aux 3 relay LED solid (not flashing)
30
Alarm LED solid (not flashing)
31
Program LED solid (not flashing)
32
Simulation LED solid (not flashing)
33
Alarm relay LED solid (not flashing)
34
Self test LED solid (not flashing)
35
Alarm active: phase undercurrent
36
Alarm active: phase overcurrent
37
Alarm active: neutral overcurrent
38
Alarm active: undervoltage
39
Alarm active: overvoltage
40
Alarm active: current unbalance
Note 1: This point is also reflected in the corresponding internal indication (IIN) bit in each response header.
GE Power Management

8.1.5 BINARY INPUT / BINARY INPUT CHANGE POINT LIST

PQM Power Quality Meter
8.1 DNP 3.0 PROTOCOL
EVENT CLASS
NOTES
ASSIGNED TO
Class 1
Class 1
Note 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
8