GE Power Quality Meter Series Instruction Manual page 81

Table of Contents

Advertisement

4 PROGRAMMING
]] SETPOINTS
]] S2 SYSTEM SETUP
] CURRENT/VOLTAGE
] CONFIGURATION
] ANALOG OUTPUT 4
]
] ANALOG INPUT
]
Figure 4–15: SETPOINTS PAGE 2 – SYSTEM SETUP / ANALOG INPUT
GE Power Management
]] SETPOINTS
]] S3 OUTPUT RELAYS
ANALOG IN MAIN/ALT
SELECT RELAY: OFF
ANALOG IN MAIN NAME:
MAIN ANALOG INPUT
ANALOG IN MAIN
UNITS:
mA
MAIN 4mA VALUE:
0
MAIN 20mA VALUE:
0
ANALOG IN MAIN RELAY:
OFF
ANALOG IN MAIN LEVEL:
100
ANALOG IN MAIN
DELAY: 10.0 s
ANALOG IN ALT NAME:
ALT ANALOG INPUT
ANALOG IN ALT
UNITS:
ALT 4 mA VALUE:
0
ALT 20mA VALUE:
0
ANALOG IN ALT
RELAY: OFF
ANALOG IN ALT LEVEL:
100
ANALOG IN ALT
DELAY: 10.0 s
PQM Power Quality Meter
4.3 S2 SYSTEM SETUP
4.3.3 ANALOG INPUT
Range: AUX1, AUX2, AUX3, OFF
Range: 20 alphanumeric characters
Range: 10 alphanumeric characters
Range: 0 to 65000; Step: 1
Range: 0 to 6500; Step: 1
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 65000; Step: 1
Range: 0.5 to 600.0 s
Step: 0.5 s
Range: 20 alphanumeric characters
Range: 10 alphanumeric characters
Range: 0 to 65000
Step: 1
Range: 0 to 6500
Step 1
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 65000
Step: 1
Range: 0.5 to 600.0 s
Step: 0.5 s
4
4-25