Specifications; Pqm Specifications - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

1 OVERVIEW

1.3 SPECIFICATIONS

CURRENT INPUTS
CONVERSION:
true rms, 64 samples/cycle
CT INPUT:
1 A and 5 A secondary
BURDEN:
0.2 VA
20 × CT for 1 sec.
OVERLOAD:
100 × CT for 0.2 sec.
RANGE:
1 to 150% of CT primary
FREQUENCY:
up to 32
ACCURACY:
±0.2% of full scale
VOLTAGE INPUTS
CONVERSION:
true rms, 64 samples/cycle
VT PRI/SEC:
direct or 120 to 72000:69 to 240
BURDEN:
2.2 MΩ
INPUT RANGE:
20 to 600 V AC
FULL SCALE:
150/600 V AC autoscaled
FREQUENCY:
up to 32
ACCURACY:
±0.2% of full scale
TRACE MEMORY TRIGGER
INPUT
1 cycle of data (current, voltage)
TIME DELAY:
0 to 30 cycles
SAMPLING MODES
SAMPLES
INPUTS SAMPLED
/CYCLE
METERED
64
VALUES
TRACE
16
MEMORY
HARMONIC
256
SPECTRUM
SWITCH INPUTS
TYPE:
dry contacts
1000 Ω max ON resistance
RESISTANCE:
OUTPUT:
24 V DC @ 2 mA (pulsed)
GE Power Management
nd
harmonic
nd
harmonic
DURATION
AT A TIME
(cycles)
ALL
2
ALL
continuous
1
1
PQM Power Quality Meter

1.3.1 PQM SPECIFICATIONS

DURATION:
100 ms minimum
ANALOG OUTPUTS
0-1 mA
(T1 Option)
2400 Ω
MAX LOAD
MAX OUTPUT
1.1 mA
ACCURACY:
±1% of full scale reading
ISOLATION:
50 V isolated, active source
ANALOG INPUT
RANGE:
4 to 20 mA
ACCURACY:
±1% of full scale reading
INTERNAL BURDEN
250 Ω
RESISTANCE:
OUTPUT RELAYS
VOLTAGE
continuous
RESISTIVE
30 VDC
125 VDC
250 VDC
INDUCTIVE
30 VDC
(L/R=7ms)
125 VDC
250 VDC
RESISTIVE
120 VAC
250 VAC
INDUCTIVE
120 VAC
PF=0.4
250 VAC
CONFIGURATION:
Form C NO/NC
CONTACT MATERIAL:Silver Alloy
1.3 SPECIFICATIONS
OUTPUT
4-20 mA
(T20 Option)
600 Ω
21 mA
MAKE/CARRY
BREAK
0.1 sec.
5 A
30 A
5 A
5 A
30 A
0.5 A
5 A
30 A
0.3 A
5 A
30 A
5 A
5 A
30 A
0.25 A
5 A
30 A
0.15 A
5 A
30 A
5 A
5 A
30 A
5 A
5 A
30 A
5 A
5 A
30 A
5 A
1-11
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqm seriesPqm-t20-c-a

Table of Contents