8.1 DNP 3.0 PROTOCOL
Implementation Table Notes:
1. For this object, the quantity specified in the request must be exactly 1 as there is only one instance of this
object defined in the relay.
2. All static input data known to the relay is returned in response to a request for Class 0. This includes all
objects of type 1 (Binary Input) and type 30 (Analog Input).
3. The point tables for Binary Input and Analog Input objects contain a field which defines which event class
the corresponding static data has been assigned to.
4. For this object, the qualifier code must specify an index of 7 only.
5. Warm Restart (function code 14) is supported although it is not required by the DNP level 2 specification.
6. Object 1 Variation 1 always indicates ON LINE for all points.
The following table specifies the default variation for all objects returned by the relay. These are the variations
that will be returned for the object in a response when no specific variation is specified in a request.

DEFAULT VARIATIONS

Object
Description
1
Binary Input - Single Bit
2
Binary Input Change With Time
10
Binary Output Status
12
Control Relay Output Block
20
16-Bit Binary Counter Without Flag
21
16-Bit Frozen Counter Without Flag
30
16-Bit Analog Input Without Flag
32
16-Bit Analog Input Change Without Time
The following internal indication bits are supported:
CHARACTER
POSITION
0
8
0
0
0
0
1
8-4
BIT
DESCRIPTION
POSITION
7
Device Restart -- set when PQM powers up, cleared by writing zero to object 80
4
Need Time -- set whenever the PQM has a "CLOCK NOT SET" alarm, cleared by
setting the clock
1
Class 1 -- indicates that class 1 events are available
2
Class 2 -- indicates that class 2 events are available
3
Class 3 -- indicates that class 2 events are available
3
Buffer Overflow -- generally indicates that the host has not picked up the event
data often enough
PQM Power Quality Meter
8 DNP COMMUNICATIONS
8.1.3 DEFAULT VARIATIONS
Default Variation
1
2
2
1
6
10
4
2

8.1.4 INTERNAL INDICATION BITS