GE Power Quality Meter Series Instruction Manual page 205

Table of Contents

Advertisement

7 MODBUS COMMUNICATIONS
Table 7–10: PQM MEMORY MAP (Sheet 25 of 40)
GROUP
ADDR
DESCRIPTION
(HEX)
EVENT
0B0C
Record #N Sc (low)
RECORD
0B0D
Record #N PFc
continued
0B0E
Record #N P3 (high)
0B0F
Record #N P3 (low)
0B10
Record #N Q3 (high)
0B11
Record #N Q3 (low)
0B12
Record #N S3 (high)
0B13
Record #N S3 (low)
0B14
Record #N PF3
0B15
Record #N Frequency
0B16
Record #N Positive kWh (high)
0B17
Record #N Positive kWh (low)
0B18
Record #N Negative kWh (high)
0B19
Record #N Negative kWh (low)
0B1A
Record #N Positive kvarh (high)
0B1B
Record #N Positive kvarh (low)
0B1C
Record #N Negative kvarh (high)
0B1D
Record #N Negative kvarh (low)
0B1E
Record #N kVAh (high)
0B1F
Record #N kVAh (low)
0B20
Record #N Ia Demand
0B21
Record #N Ib Demand
0B22
Record #N Ic Demand
0B23
Record #N In Demand
0B24
Record #N P3 Demand (high)
0B25
Record #N P3 Demand (low)
0B26
Record #N Q3 Demand (high)
0B27
Record #N Q3 Demand (low)
0B28
Record #N S3 Demand (high)
0B29
Record #N S3 Demand (low)
0B2A
Record #N Ia THD
0B2B
Record #N Ib THD
0B2C
Record #N Ic THD
0B2D
Record #N In THD
0B2E
Record #N Van THD
0B2F
Record #N Vbn THD
0B30
Record #N Vcn THD
0B31
Record #N Vab THD
0B32
Record #N Vbc THD
0B33
Record #N Analog Input (high)
0B34
Record #N Analog Input (low)
0B35
Record #N Trace Memory Trigger Cause
0B36
Record #N Internal Fault Error Code
0B37
Reserved
Notes:
* Data type depends on the Command Operation Code.
*** Maximum Setpoint value represents "OFF".
***** Maximum Setpoint value represents "UNLIMITED".
GE Power Management
RANGE
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
** Any valid Actual Values or Setpoints address.
**** Minimum Setpoint value represents "OFF".
PQM Power Quality Meter
7.3 MODBUS MEMORY MAP
STEP
UNITS and
FORMAT
VALUE
SCALE
---
0.01 x kVA
F3
---
0.01 x PF
F2
---
0.01 x kW
F4
---
0.01 x kW
F4
---
0.01 x kvar
F4
---
0.01 x kvar
F4
---
0.01 x kVA
F3
---
0.01 x kVA
F3
---
0.01 x PF
F2
---
0.01 x Hz
F1
---
kWh
F3
---
kWh
F3
---
kWh
F3
---
kWh
F3
---
kvarh
F3
---
kvarh
F3
---
kvarh
F3
---
kvarh
F3
---
kVAh
F3
---
kVAh
F3
---
A
F1
---
A
F1
---
A
F1
---
A
F1
---
0.01 x kW
F4
---
0.01 x kW
F4
---
0.01 x kvar
F4
---
0.01 x kvar
F4
---
0.01 x kVA
F3
---
0.01 x kVA
F3
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
0.1 x %
F1
---
---
F3
---
---
F3
---
---
F41
---
---
F108
FACTORY DEFAULT
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7-39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pqm seriesPqm-t20-c-a

Table of Contents