8.1 DNP 3.0 PROTOCOL
Point list for: Binary Counters (object 20)
Frozen Counters (object 21)
Counter Change Event (object 22)
Frozen Counter Events (object 23)
Point
Modbus
Num
Register
0
0450
1
0452
2
0454
3
0456
4
0460
5
03D0
6
03D2
7
03D4
8
03D6
9
03D8
10
03DA
11
03DC
12
03DE
Only counter points 0 to 4 can be cleared using function codes 9 and 10, and doing so disturbs the
totals presented on the display and via Modbus communications. In general, the binary output points
which clear data should be used if it is necessary to clear any of these counters.
NOTE
8
8-14
Description
Pulse Input 1
Pulse Input 2
Pulse Input 3
Pulse Input 4
Totalized Pulse Input
3 Phase Positive Real Energy
Used
3 Phase Negative Real Energy
Used
3 Phase Positive React.
Energy Used
3 Phase Negative React.
Energy Used
3 Phase Apparent Energy
Used
3 Phase Energy Used in Last
24 h
3 Phase Energy Cost Since
Reset
3 Phase Energy Cost Per Day
PQM Power Quality Meter

8.1.8 POINT LIST FOR COUNTERS

Unit
Deadband
Format
-
-
-
-
-
-
-
-
-
-
kWh
-
kWh
-
kvarh
-
kvarh
-
kVAh
-
kWh
-
cents
-
cents
-
8 DNP COMMUNICATIONS
Event class point
code
assigned to
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
F3
-
GE Power Management