4.4 S3 OUTPUT RELAYS

4.4 S3 OUTPUT RELAYS
]] SETPOINTS
]] S3 OUTPUT RELAYS
MESSAGE
MESSAGE
] ALARM RELAY
]
MESSAGE
MESSAGE
] AUXILIARY RELAY 1
4
]
MESSAGE
MESSAGE
] AUXILIARY RELAY 2
]
MESSAGE
MESSAGE
] AUXILIARY RELAY 3
]
MESSAGE
MESSAGE
] END OF PAGE S3
]
NON-FAILSAFE: The relay coil is not energized in its non-active state. Loss of control power will cause the
relay to remain in the non-active state. That is, a non-failsafe alarm relay will not cause an
alarm on loss of control power. Contact configuration in the Wiring Diagrams is shown with
relays programmed non-failsafe and control power not applied.
FAILSAFE: The relay coil is energized in its non-active state. Loss of control power will cause the relay
to go into its active state. That is, a failsafe alarm relay will cause an alarm on loss of
control power. Contact configuration is opposite to that shown in the Wiring Diagrams for
relays programmed as failsafe when control power is applied.
4-34
SETPOINT
]] SETPOINTS
]] S4 ALARMS/CONTROL
MESSAGE
ALARM OPERATION:
NON-FAILSAFE
ALARM ACTIVATION:
UNLATCHED
MESSAGE
AUX1 OPERATION:
NON-FAILSAFE
AUX2 ACTIVATION:
UNLATCHED
MESSAGE
AUX2 OPERATION:
NON-FAILSAFE
AUX2 ACTIVATION:
UNLATCHED
MESSAGE
AUX3 OPERATION:
NON-FAILSAFE
AUX3 ACTIVATION:
UNLATCHED
Figure 4–21: SETPOINTS PAGE 3 – OUTPUT RELAYS
PQM Power Quality Meter
4 PROGRAMMING

4.4.1 DESCRIPTION

Range: NON-FAILSAFE, FAILSAFE
Range: UNLATCHED, LATCHED
Range: NON-FAILSAFE, FAILSAFE
Range: UNLATCHED, LATCHED
Range: NON-FAILSAFE, FAILSAFE
Range: UNLATCHED, LATCHED
Range: NON-FAILSAFE, FAILSAFE
Range: UNLATCHED, LATCHED
GE Power Management