7.3 MODBUS MEMORY MAP
Table 7–10: PQM MEMORY MAP (Sheet 36 of 40)
GROUP
ADDR
(HEX)
PULSE
11B8
INPUT
11B9
ALARMS
11BA
11BB
11BC
11BD
11BE
11BF
11C0
11C1
11C2
11C3
11C4
to
11C7
SIMULATION
11C8
11C9
11CA
11CB
11CC
11CD
11CE
11CF
11D0
11D1
11D2
11D3
11D4
11D5
7
11D6
11D7
11D8
11D9
11DA
11DB
11DC
11DD
11DE
11DF
11E0
11E1
11E2
11E3
Notes:
* Data type depends on the Command Operation Code.
*** Maximum Setpoint value represents "OFF".
***** Maximum Setpoint value represents "UNLIMITED".
7-50
DESCRIPTION
Pulse Input 2 Relay
Pulse Input 2 Level
Pulse Input 2 Delay
Pulse Input 3 Relay
Pulse Input 3 Level
Pulse Input 3 Delay
Pulse Input 4 Relay
Pulse Input 4 Level
Pulse Input 4 Delay
Totalized Pulse Input Relay
Totalized Pulse Input Level
Totalized Pulse Input Delay
Reserved
Reserved
Current/Voltage Simulation
Current/Voltage Simulation Time
Phase A Current
Phase B Current
Phase C Current
Neutral Current
Vax Voltage
Vbx Voltage
Vcx Voltage
Phase Angle
Analog Output Simulation
Analog Output Simulation Time
Analog Output 1
Analog Output 2
Analog Output 3
Analog Output 4
Analog Input Simulation
Analog Input Simulation Time
Analog Input
Switch Input Simulation
Switch Input Simulation Time
Switch Input A
Switch Input B
Switch Input C
Switch Input D
Reserved
Reserved
Reserved
PQM Power Quality Meter
7 MODBUS COMMUNICATIONS
RANGE
STEP
UNITS and
VALUE
SCALE
0 to 4
1
---
1 to 65000
1
---
5 to 6000
5
0.1 x s
0 to 4
1
---
1 to 65000
1
---
5 to 6000
5
0.1 x s
0 to 4
1
---
1 to 65000
1
---
5 to 6000
5
0.1 x s
0 to 4
1
---
1 to 65000
1
---
5 to 6000
5
0.1 x s
0 to 1
1
---
5 to 305
5
min
0 to 10000
1
A
0 to 10000
1
A
0 to 10000
1
A
0 to 10000
1
A
0 to 65000
1
V
0 to 65000
1
V
0 to 65000
1
V
0 to 359
1
degrees
0 to 1
1
---
5 to 305
5
min
0 to 1201***
1
0.1 x %
0 to 1201***
1
0.1 x %
0 to 1201***
1
0.1 x %
0 to 1201***
1
0.1 x %
0 to 1
1
---
5 to 305
5
min
40 to 201
1
0.1 x mA
0 to 1
1
---
5 to 305
5
min
0 to 1
1
---
0 to 1
1
---
0 to 1
1
---
0 to 1
1
---
** Any valid Actual Values or Setpoints address.
**** Minimum Setpoint value represents "OFF".
FORMAT
FACTORY DEFAULT
F29
0=OFF
F1
100
F1
100=10.0 s
F29
0=OFF
F1
100
F1
100=10.0 s
F29
0=OFF
F1
100
F1
100=10.0 s
F29
0=OFF
F1
100
F1
100=10.0 s
F11
0=OFF
*****
F1
15 min
F1
0 A
F1
0 A
F1
0 A
F1
0 A
F1
0 V
F1
0 V
F1
0 V
F1
0 degrees
F11
0=OFF
*****
F1
15 min
F1
1201=OFF
F1
1201=OFF
F1
1201=OFF
F1
1201=OFF
F11
0=OFF
*****
F1
15 min
F1
201=OFF
F11
0=OFF
*****
F1
15 min
F27
0=OPEN
F27
0=OPEN
F27
0=OPEN
F27
0=OPEN
GE Power Management