Electrical; External Connections - GE Power Quality Meter Series Instruction Manual

Table of Contents

Advertisement

2.2 ELECTRICAL

2.2 ELECTRICAL
Signal wiring is to Terminals 21 to 51. These terminals accommodate wires sizes up to 12 gauge. Please note
that the maximum torque that can be applied to terminals 21 to 51 is 0.5 Nm (or 4.4 in ·lb.) . CT, VT, and control
power connections are made using Terminals 1 to 20. These #8 screw ring terminals accept wire sizes as large
as 8 gauge. Consult the wiring diagrams for suggested wiring. A minimal configuration includes connections for
control power, phase CTs/VTs, and the alarm relay; other features can be wired as required. Considerations for
2
wiring each feature are given in the sections that follow.
Table 2–2: PQM EXTERNAL CONNECTIONS
VT / CONTROL POWER ROW
1
V1 Voltage input
2
V2 Voltage input
3
V3 Voltage input
4
Vn Voltage input
5
Filter ground
6
Safety ground
7
Control neutral (–)
8
Control live (+)
2-4
CT ROW
9
Phase A CT 5A
10
Phase A CT 1A
11
Phase A CT COM
12
Phase B CT 5A
13
Phase B CT 1A
14
Phase B CT COM
15
Phase C CT 5A
16
Phase C CT 1A
17
Phase C CT COM
18
Neutral CT 5A
19
Neutral CT 1A
20
Neutral CT COM
PQM Power Quality Meter
2 INSTALLATION

2.2.1 EXTERNAL CONNECTIONS

SIGNAL UPPER ROW
21
Analog shield
22
Analog in –
23
Analog in +
24
Analog out com
25
Analog out 4+
26
Analog out 3+
27
Analog out 2+
28
Analog out 1+
29
Switch 4 input
30
Switch 3 input
31
Switch 2 input
32
Switch 1 input
33
+24 V DC switch com
34
Aux3 relay NC
35
Aux3 relay COM
36
Aux3 relay NO
37
Aux2 relay NC
38
Aux2 relay COM
39
Aux2 relay NO
40
Aux1 relay NC
41
Aux1 relay COM
42
Aux1 relay NO
43
Alarm relay NC
44
Alarm relay COM
45
Alarm relay NO
46
Comm 1 COM
47
Comm 1 –
48
Comm 1 +
49
Comm 2 COM
50
Comm 2 –
51
Comm 2 +
GE Power Management