Slew Rate & Minimum Transient Time; Start/Stop Sink Current - Chroma 63610-80-20 Operation & Programming Manual

Programmable dc electronic load
Table of Contents

Advertisement

Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3.8 Slew Rate & Minimum Transient Time
Slew rate is defined by the change in current over time. A programmable slew rate allows a
controlled transition from one load setting to another to minimize the induced voltage drops
on inductive power wiring, or control the induced transients on a test device. If the transient
from one setting to another is large, the actual transient time can be calculated by dividing
the current transition by the slew rate. The actual transition time is defined as the time
required for the change of input from 10% to 90% or from 90% to 10% of the programmed
excursion. If the transition from one setting to another is small, the small signal bandwidth of
Load will limit the minimum transition time for all programmable slew rates. Because of the
limit, the actual transition time is longer than the expected time based on the slew rate.
Therefore, both minimum transition time and slew rate must be considered when determining
the actual transition time. The minimum transition time is from 10μs in the CC mode and CC
dynamic mode slew rate setting.
In order to prevent the voltage transient of UUT from damaging the
Load, the electronic short function is not available in each mode for Low
and Middle current range.

3.9 Start/Stop Sink Current

To simulate the transient characteristics of load to UUT, the critical problems are when and
how the Load starts sinking current from UUT. You may set the conducting voltage Von to
solve the problems. The Load will start or stop sinking current when the UUT output voltage
reaches the Von voltage. You can start sinking current when the load is ON and the input
voltage of the module is over Von voltage, but stop sinking when load is OFF or the input
voltage is below Von voltage. See Figure 3-17 and Figure 3-18 for start/stop sinking current.
There are two operation modes for Von control, latch and non-latch. Latch means that when
voltage is over Von voltage, Load will start sinking current continuously in spite of input
voltage drop is below Von voltage. Non-latch means that when input voltage is below Von
voltage, Load will stop sinking current. The Von voltage and its operation mode are set in
configuration.
3-14

Advertisement

Table of Contents
loading

Table of Contents