Instance
Byte
Access
read
140
30 to 49
Write,
read
141
40 to 49
Write,
read
57
0 to 49
Read
50 to 65
Read
66
Read
167
0 to 49
Read
50
Read
51
Read
52 to 111
Read
The data type of supported assemblies is BYTE which means strings of 8 bits each. The naming in
Logix Designer is SINT, which has the same size of 8 bits each.
If PLC requires a configuration assembly, any value or blank can be used for assembly instance. Si-
ze of the configuration assembly shall be zero.
Please use assembly instances from Table "Overview of Assembly data bytes [ch. 8.5.1, p. 97]" for In-
put and Output. These settings can be used in generic EtherNet module configuration in Logix De-
signer which can be seen in the illustration below.
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Data type
Description
mosPLAN  6 (see [ch. 8.5.2, p. 99])
BYTE[20]
Logic output bytes, configuration
via Input data block 4 and 5 in
samosPLAN  6 (see [ch. 8.5.2, p. 99])
BYTE[10]
Logic output bytes, configuration
via Input data block 5 in samos-
PLAN  6 (see [ch. 8.5.2, p. 99])
BYTE[50]
Logic output bytes, configuration
via Output data block 1 in samos-
PLAN  6 (see [ch. 8.5.3, p. 100])
BYTE[16]
Values of the input terminals Ix
BYTE
Input and output state
BYTE[50]
Logic output bytes, configuration
via Output data block 1 in samos-
PLAN  6 (see [ch. 8.5.3, p. 100])
BYTE
Bit 7: Input state
Bit 6: Output state
Bit 5: Error code ≠ 0
BYTE
System mode
State bytes of the controller module
BYTE[60]
(Instance 3 of class 120 [ch. 8.4.8.3, p.
94]), output data set 3 (siehe [ch.
8.5.3, p. 100])
EtherNet/IP gateway
Size
Data range
Bytes
1 to 20
0 to 0xff
Bytes
1 to 10
0 to 0xff
Bytes
1 to 50
0 to 0xff
Bytes
1 to 16
0 to 0xff
Bytes
1 byte
0x00, 0x40,
0x80, 0xc0
1 to 50
0 to 0xff
Bytes
1 byte
0x00, 0x40,
0x80, 0xc0
1 byte
1, 2, 3, 4, 5, 7,
21
60 byte
0 to 0xff
98