Wieland samos PRO Manual page 72

Compact-gateways
Table of Contents

Advertisement

Table 34: Readable I&M information
Name
MANUFACTURER_ID (Vendor
ID)
ORDER_ID (Order ID)
SERIAL_NUMBER
(IM_Serial_Number)
HARDWARE_REVISION
(IM_Hardware_Revision)
SOFTWARE_REVISION
(IM_Software_Revision)
Device ID
REV_COUNTER
(IM_Revision_Counter)
PROFILE_ID (IM_Profile_ID)
PROFILE_SPECIFIC_TYPE
(IM_Profile_Specific_Type)
IM_VERSION (IM_Version)
IM_SUPPORTED
(IM_Supported)
TAG_FUNCTION
TAG_LOCATION
INSTALLATION_DATE
(IM_Date)
DESCRIPTOR (IM_Descriptor) 54 bytes
IM_Signature
1)
Subject to changes
Alarms
Alarms can be acyclically read using the PROFINET IO alarm infrastructure. When an error in the sa-
mosPRO system occurs, the PROFINET IO gateway sends a corresponding diagnostics alarm to the
network. The details of the diagnostics alarm (text and help) are then available through the SIMATIC
PLC interface. The RALRM (SFB54) function block in OB82 (diagnostics interrupt) allows you to make
the details of the sent alarm directly available in the PLC program.
NOTICE
All alarms are output to module 0.
The cause of the alarm is displayed by an error message from the GSDML file.
The possible causes of an alarm can be found in the software manual, Section "List of all error
messages".
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Size
Value range
2 bytes
397 = 0x18D
"R1.190.1310.0 + 51 blank spaces and
64 bytes
"R1.190.1320.0 " + 51 blank spaces
8 bytes
"16010001" to "99129999"
2 bytes
101 to 9999
6 to 9 Bytes
"V0.1.0" to "V99.99.99"
1320
2 bytes
0 to 65535
2 bytes
0x0000 (Non-profile)
2 bytes
0x0003 (IO modules)
2 bytes
1
2 bytes
10 (= 0b1010)
32 bytes
32 Bytes à 0x20..0x7E
22 bytes
32 Bytes à 0x20..0x7E
16 bytes
54 Byte à 0x00..0xFF
54 bytes
54 Byte à 0x00..0xFF
PROFINET IO-Gateway
I&M
Storage locati-
on
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SD card
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
0
SP-COP2-ENI
1
SD card
1
SD card
2
SD card
1)
3
SD card
4
SD card
72

Advertisement

Table of Contents
loading