Illustration 11: Configuration dialog for the IP data and the device name
NOTICE
The format of the device name must correspond to the specification of the PROFINET stan-
dard.
• Ensure that the address for the default gateway matches the address set by the PLC for the
gateway. If no router is used, then Siemens Step 7 uses the same IP address for the default ga-
teway as for the SP-COP2-ENI module.
• If a project file with an active PROFINET IO is provided on the SP-COP2-ENI module, then only
one device in samosPLAN  6 can be found by USB. If you would like to use the Ethernet to
connect with the SP-COP2-ENI module then select Edit in the Connect dialog, where you then
set the IP address of the SP-COP2-ENI module.
Set the IP address using the software
The IP address is typically assigned by the PROFINET IO controller (e.g. PLC). The SP-COP2-ENI mo-
dule, however, also allows the configuration of the entire samosPRO system via Ethernet TCP/IP. It
can be necessary in this case to already assign an IP address to the SP-COP2-ENI before the PROFI-
NET IO network is set up. This can also be done in the configuration dialog shown above.
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
PROFINET IO-Gateway