MODBUS TCP GATEWAY

77973771
The controller module SP-COP2-ENI can be used for Modbus TCP. The internal SP-EN-MOD (Modbus
TCP Gateway) is a component of the SP-COP2-ENI device and is activated by the gateway configura-
tion:
Illustration 8: Activation of Modbus TCP on the SP-COP2-ENI module
The Modbus TCP gateway supports the following:
• Modbus TCP with master and slave operation
• Ethernet TCP/IP socket interface, polling and auto-update function
6.1

Interfaces and operation

77992459
The SP-COP2-ENI is equipped with a RJ-45 socket.
Illustration 9: Interfaces and display elements
Further information
• Here in this manual:
Diagnostics and troubleshooting [ch. 6.4, p. 60]
• In the hardware manual:
Device state and LED displays in the controller modules
6.2
Basic configuration – allocation of an IP address
78009227
The SP-COP2-ENI module is configured with the help of the samosPLAN  6 configuration software.
Step 1: Add SP-COP2-ENI module
 Start samosPLAN  6 and open the Modules docking window.
 Add the controller module SP-COP2-ENI.
Instructions: Software manual, chapter "Adding modules"
Step 2: Open configuration dialog
 Switch to the Project structure docking window.
 Click on the top element, which represents the controller.
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Modbus TCP gateway
52