The SP-COP2-ENI module is a General Purpose Discrete I/O Device. For quick installation, use the
connection Logic Output (1 to 400) and Logic/Physical Input, if your PLC supports implicit messa-
ge transmission. The following figure shows the appropriate dialog in the Logix Designer.
Illustration 16: Basic connection selected in the Logix Designer
This connection comprises up to 50 bytes for data transmission from the PLC to the SP-COP2-ENI
module (assembly instance 37). This connection comprises up to 67 bytes for data transmission
from the SP-COP2-ENI module to the PLC (assembly instance 57). The following table offers an over-
view of these data bytes.
Table 38: Data of the class 1 connection "Logic output (1 to 400) and logic/physical input"
Instance
Byte
Access
37
0 to 49
Write, read BYTE[50]
57
0 to 49
Read
50 to 65
Read
66
Read
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Data type
Description
Output bytes, configuration via
Input data block 1 to 5 in
samosPLAN  6
(More [ch. 8.5.2.1, p. 99])
BYTE[50]
Input bytes, configuration via
Output data block 1 in samos-
PLAN  6
(More [ch. 8.5.3.1, p. 100])
BYTE[16]
Bits of the input terminals
(instance 401 to 528 of attribu-
te 3 class 8, currently not listed
in samosPLAN  6 )
(More [ch. 8.5.3.1, p. 100])
BYTE
Bit 7: Input state
Bit 6: Output state
(currently not listed in samos-
PLAN  6 )
EtherNet/IP gateway
Size
Data range
1 to 50 Bytes
0 to 0xff
1 to 50 Bytes
0 to 0xff
1 to 16 Bytes
0 to 0xff
1 byte
0x00, 0x40,
0x80, 0xc0
78