Wieland samos PRO Manual page 61

Compact-gateways
Table of Contents

Advertisement

Error
The SP-COP2-ENI module does
not provide any data.
LED PWR/EC
LED LINK
LED ACT
The SP-COP2-ENI module does
not provide any data.
LED PWR/EC
LED LINK
LED ACT
MS LED
The SP-COP2-ENI module does
not provide any data.
LED PWR/EC
LED LINK
LED ACT
MS LED
The SP-COP2-ENI module does
not provide any data.
LED PWR/EC
MS LED
The SP-COP2-ENI module func-
tioned correctly after configu-
ration but suddenly provides
no more data.
LED PWR/EC
LED LINK
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Possible cause
• The SP-COP2-ENI module
has been configured for da-
ta transmission to the PLC,
Green
but no Ethernet communi-
Green
cation has been establis-
hed or the communication
is faulty.
Orange
• Duplicate IP address detec-
ted. Another network de-
vice has the same IP
address.
• Configuration required.
• The configuration has not
yet been fully transmitted.
• The module version of the
Green
controller module does not
Green
support the gateway func-
tion.
Orange
Red
(1 Hz)
• No data set was activated.
• No Ethernet communicati-
on interface was activated.
Green
Green
Orange
Green
The SP-COP2-ENI module is in
the "Stop" state.
Green
Green
(1 Hz)
• The SP-COP2-ENI module is
operated in slave mode,
the IP address is allocated
by a DHCP server.
• Following a restart of the
Green
SP-COP2-ENI module or the
Green
Modbus TCP gateway
Possible remedy
COP2-ENI module and the
PC to a network, using an
active DHCP server.
• Check the communication
settings in samosPLAN  6 .
At least one Ethernet link must
be established.
• Set up the Ethernet link on
the PC, check the Ethernet
wiring, check the Ethernet
settings in the PLC and in
samosPLAN  6 .
• If no Ethernet communica-
tion is required, deactivate
the Ethernet connections /
PLC interfaces on the SP-
COP2-ENI.
• Correct the IP address and
switch the system off and
on again.
• Configure the SP-COP2-ENI
module and transfer the
configuration to the sys-
tem.
• Wait until the configuration
has been fully transferred.
• Use the controller module
with the required module
version.
• Activate at least one data
set.
The controller module is stop-
ped.
• Start the controller module
(switch to Run mode).
• Allocate a fixed IP address
to the SP-COP2-ENI modu-
le.
or
• Reserve a fixed IP address
for the SP-COP2-ENI modu-
61