Table 46: Overview of the discrete output group object (0x1D) supported by the SP-COP2-ENI module
Class
Instance
Attribute
30
0 = Class
1
30
0 = Class
2
30
0 = Class
3
30
0 = Class
6
30
0 = Class
7
30
1
1
30
1
2
30
1
3
30
1
4
30
1
5
8.4.7

PCCC Object

80119691
PCCC (pronounced "P C Cube") is used in several PLCs from Rockwell Automation/Allen Bradley,
which still continue to be used. It was developed before CIP and EtherNet/IP were defined. PCCC te-
legrams are either:
a) Encapsulated in CIP packages (e.g. via EtherNet/IP)
b) The encapsulation of CIP packages.
The SP-COP2-ENI module supports the encapsulation of PCCC data in CIP packages, as described
above under b). For this, the class ID 0x67 = 103 was specified.
The PCCC commands listed in the following table are supported by the SP-COP2-ENI module.
All PCCC-related data with a size of 16 bits (word) are available in the "Little Endian" format. This
means that the byte with the lowest value is executed first.
Table 47: PCCC commands supported by the SP-COP2-ENI module
Type
CMD
FNC
Description
PLC-5
0x0f
0x00 Word Range Write [ch. 8.4.7.2, p. 89]
PLC-5
0x0f
0x01 Word Range Read [ch. 8.4.7.3, p. 90]
PLC-5
0x0f
0x67 Typed Write [ch. 8.4.7.4, p. 90]
PLC-5
0x0f
0x68 Typed Read [ch. 8.4.7.5, p. 91]
SLC
0x0f
0xa1 Protected Typed Logical Read with 2 Address Fields [ch.
8.4.7.6, p. 92]
SLC
0x0f
0xa2 Protected Typed Logical Read with 3 Address Fields [ch.
8.4.7.8, p. 93]
SLC
0x0f
0xa9 Protected Typed Logical Write with 2 Address Fields [ch.
8.4.7.7, p. 93]
0xaa Protected Typed Logical Write with 3 Address Fields [ch.
SLC
0x0f
8.4.7.9, p. 93]
80135307
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Access
Data type
Description
Read
UINT
Revision of the class
Read
UINT
Max. instance
Read
UINT
Number of instances
Read
UINT
Max. class attribute ID
Read
UINT
Max. instance attribute ID
Read
USINT
Number of attributes
Read
USINT[6]
List of support attributes
Read
USINT
Number of bound instances
Read
UINT[56]
Bound instances
Read
BOOL
Group state of all output terminals
(state of instances 529 to 584 of class
8)
EtherNet/IP gateway
Data range
1
1
1
7
6
6
{1, 2, 3, 4, 5, 6}
56
{1, ..., 56}
0 = No error,
1 = Error
Command supported by
PLC-3, PLC-5, PLC-5/250
PLC-3, PLC-5, PLC-5/250
SLC 5/03, SLC 5/04, PLC 5,
PLC-5/250, PLC-5/VME
SLC 5/03, SLC 5/04, PLC 5,
PLC-5/250, PLC-5/VME
MicroLogix-1000, SLC 500,
SLC 5/03, SLC 5/04, PLC 5
MicroLogix-1000, SLC 500,
SLC 5/03, SLC 5/04
88