Wieland samos PRO Manual page 109

Compact-gateways
Table of Contents

Advertisement

LED
PWR
Table 72: Address switch of the SP-PROFIBUS-DP module
Switches
× 10
× 1
How to set the PROFIBUS-DP address with the aid of the hardware address switches:
 Use the hardware address switches at the front of the system to set the PROFIBUS-DP address.
 Switch the samosPRO system off and on again.
How to set the PROFIBUS-DP address in the software:
 Set the two hardware address switches on the front of the device to "00".
 Launch samosPLAN  6 .
 Read in the hardware configuration, including the PROFIBUS-DP gateway.
Instructions: Software manual, chapter "Connecting to the safety controller"
 Open the Modules docking window and select the SP-PB-DP module.
⇨ You see the configuration dialog for the SP-PB-DP module.
 Also open the Properties docking window.
 Enter the desired value for the Control address parameter under Communication.
NOTICE
You can set an address within the 1 ... 99 range with the aid of the hardware address switches.
• You can set an address within the 3 ... 125 range with the aid of the samosPLAN  6 .
• The PROFIBUS master cannot overwrite the address.
• An amended address setting will only become effective once you have switched off the sa-
mosPRO system and switched it on again.
• In the online mode, you can read out the address set at the PROFIBUS-DP gateway by clicking
on the Read button above the PROFIBUS address field.
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Meaning
Critical error on another module
Red
No power supply
Off
Power supply switched on, no error
Green
Critical error
Red
Function
Address switch 1
Rotary switch with 10 positions for setting the module address
(in tens)
Address switch 2
Rotary switch with 10 positions for setting the module address
(in units)
PROFIBUS DP gateway
109