Error
MS LED
The SP-CANopen module is in
the critical error state
LED PWR
LED NS
MS LED
The SP-CANopen / the sa-
mosPRO system is in the Criti-
cal error state.
LED PWR
LED NS
MS LED
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Possible cause
/
Red / green
• Internal equipment error
on the SP-CANopen modu-
le.
Green
• The module version of the
controller module does not
Red
support samosPRO gate-
ways.
Red (2 Hz)
• The SP-CANopen module is
not properly connected to
the samosPRO modules.
• The module connection
Red
plug is dirty or damaged.
Off
• Another samosPRO module
has an internal critical er-
Red
ror.
CANopen gateway
Possible remedy
× heartbeat producer time).
• Check the diagnostic mes-
sages with the aid of the
samosPLAN  6 .
• Reset the samosPRO sys-
tem.
• Switch the samosPRO
system's power supply off
and on again.
• Check the diagnostic mes-
sages with the aid of the
samosPLAN  6 .
• Use the controller module
with the required module
version.
• If the error persists, replace
the gateway.
• Plug the SP-CANopen mo-
dule in correctly.
• Clean the connection plug
and socket.
• Switch on the power supp-
ly
• once again.
• Check the other samosPRO
modules.