Wieland samos PRO Manual page 181

Compact-gateways
Table of Contents

Advertisement

Error
MS LED
LINK
(ETHERCAT-
IN)
Controller errors
MS LED
RUN
ERR
LINK
The SP-EN-ETC does not
provide any input data.
MS LED
LINK
LINK
The SP-EN-ETC does not
provide any input data.
MS LED
RUN
LINK
The SP-EN-ETC does not
provide any input data.
MS LED
RUN
LINK
The SP-EN-ETC does not
provide any input data.
MS LED
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Possible cause
port, EtherCAT not active.
/
Red / green
Green
• Incorrect EtherCAT confi-
guration, gateway is
addressed with incorrect
Red
data.
• Gateway is in Pre-Op state.
Green /
flashing
Red /
flashing
Green
After switch-on:
• Gateway state is Init.
/
Red / green
Green
Green
After switch-on:
• Gateway state is Pre-Op.
/
Red / green
Green
Green
• Gateway state is Safe-Op.
/
Red / green
Green/flash
Green
• No EtherCAT data, but
there is a bus connection to
next EtherCAT slave.
/
Red / green
EtherCAT Gateway
Possible remedy
Init state
• Check network and device
configuration.
• Switch power off and back on.
• Switch EtherCAT to Op state.
• Switch EtherCAT to Op state.
• Switch EtherCAT to Op state.
• Re-start EtherCAT master or
supply master with power.
• Check RJ45 cable.
• Repair interruption to the
EtherCAT network.
181