Equipment Variants; Data Transferred To The Network (Network Input Data Sets) - Wieland samos PRO Manual

Compact-gateways
Table of Contents

Advertisement

Info
• You can find the module version on the type plate of the modules.
• You will find the samosPLAN  6 software version in the main menu.
• The latest software version is available in the Internet at the following address
http://www.wielandinc.com/.
• Newer modules are backwards-compatible, which means that each module can be replaced
with a module having a higher module version.
• You can find the date of manufacture for a device on the type plate in the S/N field in the format
<Product no.>yywwnnnnn (yy = year, ww = calendar week).

Equipment variants

3.2
77455755
There are three samosPRO gateways for various network types.
The Modbus TCP / PROFINET IO and EtherNet/IP gateway of the SP-COP2-ENI controller module or
the external SP-EN-ETC gateway are suitable for Ethernet networks. The SP-PROFIBUS-DP gateway
and the SP-CANopen gateway are external field bus gateways without an Ethernet function.
Restrictions for Ethernet connections
• The Ethernet connection can only be linked to autonomous networks or demilitarized zones
(DMZ).
• The device must never be connected directly to the Internet.
ATTENTION
Always use secure data tunnels (VPN) to exchange data via the Internet.
Table 9: Equipment variants and their main characteristics
Gateway
SP-EN-MOD
SP-EN-PN
SP-EN-IP
SP-PROFIBUS-DP
SP-CANopen
SP-EN-ETC
NOTICE
You will find the manufacturing date of a device on the type label in the S/N field in the format
yywwnnnn (yy = year, ww = calendar week, nnnn = sequential serial number within a calendar
week).
3.3

Data transferred to the network (network input data sets)

77477899
Available data
The samosPRO gateways can provide the following data:
• Process data
– Logic results from the samosPRO safety controller (see Routing table [ch. 5.1.3, p. 43])
– Input values (HIGH/LOW) for all samosPRO input expansion modules in the system
– Output values (HIGH/LOW) for all samosPRO input/output expansion modules (see Module
state / input and output values [ch. 3.3.1, p. 24])
– Output data from another network, i.e. data received from a second gateway in the sa-
mosPRO system (see Transmission of data from a second network [ch. 3.3.3, p. 25])
• Diagnostics
– Test values (CRCs): (see Configuration test values (CRCs) [ch. 3.3.4, p. 25])
– Error and state information: Error and state information for the modules [ch. 3.3.5, p. 26]
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Network type
Modbus TCP with master and
slave operation
PROFINET IO device
EtherNet/IP device
PROFIBUS DP slave
CANopen slave
EtherCAT slave
Product description
Ethernet IP socket interface
Client/Server on TCP Port 502
UDP ports 34964, 49152
TCP port 44818, UDP port 2222
- -
- -
- -