PROFINET configuration of the gateway - which data are transferred

79202571
Cyclical data
The physical I/O modules are not presented in the PROFINET IO hardware catalog as typical hard-
ware modules in the network. Instead, the data provided by the samosPRO system has been arran-
ged in various data blocks. Every data block represents a module in the PROFINET IO hardware ca-
talog. The GSDML supports 13 Slots in which the modules can be placed. This makes is possible to
use each data set one time (see illustration "Configuration" [ch. 7.4, p. 71]).
Process data from module to PLC
The SP-COP2-ENI module provides 5 input data blocks (virtual device modules) which contain the
process image. These can be exclusively placed in each corresponding slot 16 to 20.
NOTICE
Input data blocks 1 to 4 each contain 12 bytes, while input data block 5 contains 2 bytes.
The content of the input data blocks can be freely selected. The data assignment in samosPLAN  6 is
pre-configured in accordance with the following:
Table 33: Predefined content of input data block 1 to 5 of the SP-COP2-ENI module
Data block 1
Byte no. per
Input data
data block
Byte 0
Input values SP-
COP2-ENI
Input values SP-
Byte 1
COP2-ENI
Input values SP-
Byte 2
COP2-ENI
Byte 3
Output values SP-
COP2-ENI
Byte 4
Logic data values I/O module 5
Byte 5
Logic data values I/O module 6
Byte 6
Logic data values I/O module 7
Byte 7
Logic data values I/O module 8
Byte 8
Logic data values I/O module 9
Logic data values I/O module 10
Byte 9
Logic data values I/O module 11
Byte 10
Byte 11
Logic data values I/O module 12
Length
12 bytes
Byte offset
0
1 byte for data set 1 is available for every expansion module. The input values show the state of the
preliminary evaluation of the I/O module. This corresponds to the state of the element in the con-
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Data block 2
Data block 3
Input data
Input data
I/O module 1
I/O module 1
input values
output values
I/O module 2
I/O module 2
input values
output values
I/O module 3
I/O module 3
input values
output values
I/O module 4
I/O module 4
input values
output values
I/O module 5
input values
output values
I/O module 6
input values
output values
I/O module 7
input values
output values
I/O module 8
input values
output values
I/O module 9
input values
output values
I/O module 10
input values
output values
I/O module 11
input values
output values
I/O module 12
input values
output values
12 bytes
12 bytes
12
24
PROFINET IO-Gateway
Data block 4
Data block 5
Input data
Input data
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not available
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
12 bytes
2 bytes
36
48
69