Wieland samos PRO Manual page 155

Compact-gateways
Table of Contents

Advertisement

60C:
8:
40:
00 31:
0F:
Gateway response:
CAN-ID
58C
58C:
8:
42:
00 31:
04:
FB:
FE:
Reading of error from the error history in SDO 1003:
PLC requests:
CAN-ID
60C
60C:
8:
40:
03 10:
01:
Gateway response:
CAN-ID
58C
58C:
8:
42:
03 10:
01:
01:
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
Identifier (600 + C)
Data length code: This is followed by 8 bytes
Expedited upload requirement
Index 3100
Subindex 0F = Module to position 12 (module position = subindex - 1
(see also table "Content of SDO 3100" [ch. 10.10, p. 147])
DLC
DATA
8
42
00
Identifier (580 + C)
Data length code: This is followed by 8 bytes
Upload response, size of data set is not shown
Index 3100
Subindex: Module to Position 1
(see table "Content of SDO 3100" [ch. 10.10, p. 147])
Error byte M5, Bit 2 = 0: external error
Error byte M4, bit 0 = 0: two-channel evaluation of inputs 1–2: Error detected
(See Table "CANopen Emergency Messages" [ch. 10.6, p. 133])
DLC
DATA
8
40
03
Identifier (600 + C)
Data length code: This is followed by 8 bytes
Expedited upload requirement
Index 1003
Sub-index: last error
DLC
DATA
8
42
03
Identifier (580 + C)
Data length code: This is followed by 8 bytes
Upload response, size of data set is not shown
Index 1003
Sub-index: last error
Module status bit 8 (bit 0 of byte M4) = 0: two-channel evaluation of inputs 1–2: error
detected
31
0F
FF
10
01
00
10
01
00
CANopen gateway
FF
FE
FB
00
00
00
00
01
00
155