Wieland samos PRO Manual page 71

Compact-gateways
Table of Contents

Advertisement

Illustration 12: Configuration of the SP-COP2-ENI module
NOTICE
The input and output addresses indicate the location of the cyclical data in the memory. These can
be addressed via the absolute addresses %I and %Q in the SIEMENS TIA portal.
Acyclical data and alarms
Read out data
The PLC can read out the diagnostic data of the samosPRO system. The diagnostic information is
provided in three data sets, data sets 2, 3, and 4:
Data set 2 comprises 32 bytes and contains the project file's CRC 32. This can only be placed in slot
32.
Data set 3 comprises 60 bytes and contains the status of SP-COP2-ENI module and the individual I/O
modules. This can only be placed in slot 33. See the following to interpret the status bits in data set
3: Table "Meaning of the module status bits of the controller module" [ch. 3.3.5, p. 26] and Table "Me-
aning of the module status bits of the I/O modules" [ch. 3.3.5, p. 27]
Data set 4 (auxiliary data) comprises 60 bytes and is currently filled with reserved values. This can
only be placed in slot 34.
NOTICE
Type and source of danger
Data set 4 in Slot 34 does not function with all versions of the SIEMENS TIA portal.
Information & Management
The SP-COP2-ENI module supports the I&M information defined in the PROFINET IO specification.
The following I&M information can be read out:
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
PROFINET IO-Gateway
71

Advertisement

Table of Contents
loading

Table of Contents