Electrical Systems - House
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
8 • 3 1 2
Set Exercise period days 30 - Starts the generator regardless of any other
setting. Periodically starts the generator for maintenance reasons. The generator
should be operated at least every 30 days to lubricate the internal engine
components.
Set Maximum run time h:m - Displays an error message if the generator
operates longer than the time period set. This is only a message. To cancel the
message return to heading number "2 Generator Mode." Use the green button
to scroll to Off. Setting the time and minute to 00:00 defeats this function.
Gen Starting Details:
11. Use the down arrow on the Menu Headings button to scroll
to menu heading number 13, Gen Starting Details.
12. Use the Menu Items button to scroll down to "Set Gen warm-up
seconds." Use the Set Points buttons to set the time to 90 seconds.
If it is not set to 90 seconds, the generator will shut down
prematurely.
13. Use the Menu Items button to scroll down to "Set Post Crank
seconds." Use the Set Point buttons to set the time to 90 seconds.
If it is not set to 90 seconds, the generator will shut down
prematurely.
To Enable or Disable the Auto Gen Start Program:
After completing the programming schedule, use the green button
to return to heading number "2 Generator Mode."
• To Enable the Automatic Generator Start Feature: Press the
green button and scroll to AUTO.
• To Disable the Automatic Generator Start Feature: Press the
green button and scroll to OFF.