Siemens SINAMICS G110M Function Manual page 88

Fieldbuses
Hide thumbs Also See for SINAMICS G110M:
Table of Contents

Advertisement

Communication via EtherNet/IP
4.5 Supported objects
Supervisor Object, Instance Number: 29 hex
Supported services
Class
• Get Attribute single
Table 4- 11
No.
1
2
3
Table 4- 12
No.
3
5
6
7
9
10
11
12
13
14
15
88
Class Attribute
Service
Type
Name
get
UINT16
Revision
get
UINT16
Max Instance
get
UINT16
Num of Instances
Instance Attribute
Service
Type
Name
get, set
Bool
Run1
get, set
Bool
Net Control
get
UINT8
State
get
Bool
Running1
get
Bool
Ready
get
Bool
Fault
get
Bool
Warning
get, set
Bool
Fault reset
get
UINT16
Fault Code
get
UINT16
Warning Code
get
Bool
CtlFromNet
Instance
• Get Attribute single
• Set Attribute single
Value/explanation
STW.0 operation, clockwise rotation
Internal
0: Local
1: Network
0: Vendor Specific
1: Startup
2: Not_Ready
3: Ready
4: Enabled
5: Stopping
6: Fault_Stop
7: Faulted
ZSW1:2
1: - (Enabled and Run1) or
- (Stopping and Running1) or
- (Fault_Stop and Running1)
0 = Other state
ZSW1:0
1: - Ready or
- Enabled or
- Stopping
0 = Other state
ZSW1:3 drive fault
ZSW1:7 alarm active
STW.7 acknowledge fault
r945[0] error code
r2122[0] alarm code
Display from Net Control
1: Control from network
0: Local control
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
Fieldbuses

Advertisement

Table of Contents
loading

Table of Contents