Settings in the inverter
Procedure
To adjust the settings in the inverter, proceed as follows:
1. Make the following settings and releases so that the inverter can accept commands from
the panel:
– Set the two signal sources for OFF2 (p0844 and p0845) to 1: p0844 = 1
– Set the two signal sources for OFF3 (p0848 and p0849) to 1: p0848 = 1
– Set the releases for the ramp-up encoder
– Set the setpoint release
2. Adjust the parameters for the ON/OFF1 command from the SIMATIC panel
– Set p0840[0] = 2094.0
– Now set p2099[0] = p2900
3. Set parameters for the setpoint default
– Set
4. Actual value and status word
No further settings are required by the inverter for displaying the speed list value (r0021)
and the status word (r0052).
You have now made the settings in the inverter.
Fieldbuses
Function Manual, 01/2016, FW V4.7 SP6, A5E34229197B AC
p0845 = 1
p0849 = 1
p1140 = 1
p1141 = 1
p1142 = 1
In doing so, you interconnect the ON/OFF1 command with bit 0 of the BiCo converter
2094. The signal source of this parameter is p2099.
In doing so, you give the ON/OFF1 command by setting P2900 = 1 (ON) or 0 (OFF1)
P1070 = 1001 (fixed setpoint 1 as setpoint)
P1016 = 1 (direct selection of the speed setpoint)
P1020 = 1 (speed fixed setpoint selection, Bit 0)
Communication via PROFIBUS and PROFINET