13.3 Exchanging the module

DANGER!
If a defect in the Safety Module is detected, the converter must be put out of operation
immediately and the Safety Module must be exchanged.
CAUTION!
m The exchange of the module must only be performed by authorized and qualified
m No further changes in the configuration of the system may be made during the
m Prior to the exchange of the module, ensure that the safety module and the
Course of the exchanging process
After insertion of the Safety Module (SAF-001) into the converter and switching on the
converter, the following processes are performed in the converter and Safety
Module (SAF-001) (see also
1 Scan of the automatic parameter adjustment by the Safety Module (SAF-001).
2 Check, if the converter was equipped with a higher level Safety Module before
3 Checking the parameters with Safety Module (SAF-001). 
Operation Manual Safety Module for b maXX 5000 BM5-O-SAF-000/-001
Commissioning and exchange of the module
personnel.
exchange of the module.
converter are compatible.
For a list of the converters compatible with the Safety Module refer to the chapter
ZCompatibility list SAF-001-000-xxx–
If, the checkbox „Load automatic" is set in ProDrive on the page „Dataset
management", the parameters are automatically loaded from the safety module into
the converter.
If there is no data set in the Safety Module, the data of the converter is loaded into the
Safety Module.
module replacement (SAF-002/003).
m Converter was equipped with a Safety Module (downgrade) of higher level
The converter indicates error 2418 (module change to lower safety level). A release
of the controller is only possible by resetting of the converter with a Reset-Module.
ZDescription of the Reset-Module–
(see
m The converter was not already equipped with a higher level Safety Module (see
step 3).
If the data sets between the converter and the Safety Module (SAF-001) still are
different, this is displayed by a red LED H2 at the Safety Module, which always is on
and the error message 2403 (different parameter data on the controller and the SAF-
Module) in parameter 100.010.0.0 (Safety Module state). By acceptance with button
S1 (long-short-short-long) by the user, the parameters are copied from the controller
to the Safety Module.
on page 38.
ZFigure 27–
on page 80).
from page 61 ).