Title Manual Product Feed/Feedback Unit with analog Controller BUC64 S/A/F Version 5.02024.03a Status 2005-01-11 Copyright These operating instructions may be copied by the owner in any quantity but only for internal use. For other purposes these operating instructions and extracts thereof must not be copied or reproduced.
NTRODUCTION In this chapter we describe the first steps you should carry out after you have received your appliance. We will give you a definition of terms used throughout this documentation and we will give you information about what must be observed when using this appliance. First steps 1 check the scope of delivery, see ZPacking and Transport–...
Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Page 9
The “General terms of sale and delivery“ of Baumüller Nürnberg GmbH apply generally. Those you have available at least since the contract has been confirmed. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 10
Obligation and liability Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Hazard information shows you the dangers, which can cause injuries or even your death. Please always consider the hazard information which is given to you in this doc- umentation. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
The outline´s shade of grey reflects the severity of the hazard - darker grey means rising haz- ard. (Not every hazard information has a square representing the hazard, so we have shown it as draft here) Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
The hazard is: mechanical influence. Here the hazard may be described in detail. Here we describe what you can do to avoid the hazard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 14
The hazard is: electro-magnetic radiation. Here the hazard may be described in detail. Here we describe what you can do to avoid the hazard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Page 15
The hazard is: liquid coolant. Here the hazard may be described in detail. Here we describe what you can do to avoid the hazard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 16
The hazard is: injury of the eye caused by ricochetting particles. Here the hazard may be described in detail. Here we describe what you can do to avoid the hazard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Page 17
The hazard is: unadequate disposal. Here the hazard may be described in detail. Here we describe what you can do to avoid the hazard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Here we describe what you can do to avoid the hazard. 2.1.2.3 Command signs used carry safety gloves carry safety shoes carry eye protection carry ear protection Use this fire extinguishing agent: ABC powder. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Unauthorized reconstructions without written permission of Baumüller Nürnberg GmbH are not allowed. Disposal of the appliance The correct disposal of the appliance is described in ZDisposal– from page 79. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
The following may occur, if you do not observe this warning information: m serious personal injury m death The danger is: electricity when using a conductive fire extinguishing medium. Use this fire extinguishing agent: ABC powder Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 22
Fire fighting Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Baumüller representative if the scope of delivery is incomplete or if there is a transportation damage. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
2 K 3 m temperature interval: - 30 °C to + 70 °C ) m maximum height of drop (packaged): 0.25 m Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
With the reset X98AB: 5/6 (+24 V) error messages, which generate the basic unit are re- set. A permanent reset may not be generated. However the reset signal must be present at least 50 ms. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
A: stands for window mounting variant A (air ventilation outside the switching cabinet) m F: stands for window mounting variant F (water cooler outside the switching cabinet) figure 1: Cooling variants Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
The following figure shows the hazardous areas at each respective appliance. Use this overview to get informed about the existing hazardous areas when you learn to get famil- iar with this appliance. figure 2: hazardous areas Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
On the type key you will find only a part of the technical specifications. An overview of all technical specifications you will find in ZAppendix D - Technical Specifications– from page 95. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Description of the Unit Block switching diagrams figure 4: Block switching diagram BUC64S/A/F Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Block switching diagrams figure 5: Connections of BUC - BUS Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Description of the Unit Construction diagram figure 6: Construction diagram BUC64-300A/390A part 1 Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 32
Construction diagram figure 7: Construction diagram BUC64-300A/390A part 2 Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Description of the Unit Example for PowerOn/Off control figure 8: Example for Power On/Off control Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 34
Example for PowerOn/Off control Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Hazards caused by electricity you will find under Z6.2 Hazardous areas at installation– on page 47. figure 9: Hazardous areas during mounting Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
NOTE h If you mount a window variant (F/A), the back side may only have a maximum thickness of 6 mm. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
96). If necessary mount additional ventilators to the switching cabinet. a: free space for controller, connector and cable approx. 60 mm b: back side view *: free space figure 10: Dimensional drawing of BUC64S/A/F Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
(variant A/F only) according to the drilling figures below. * screw head figure 11: Drilling figure of BUC64S/A/F Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
- the appliance weighs approx. 70 kg. lift the appliance only with suitable equipment and/or with the help of adequate qualified per- sonnel. carry safety gloves Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
(A) 4 x M8 washers (B) 4 x (8.4 x 17) mounting distance (c) c = 7 mm figure 12: Mounting instruction of BUC64S Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Make sure not to damage the sealing at the back side of the unit. Only mount the unit if the sealing is not damaged. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Mounting the unit screws (A) 16 x M8 washers 16 x (8.4 x 17) sealing see accessories figure 13: Mounting instruction BUC64 window variant A/F Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
If coolant circulations that have been filled with a coolant-water mixture must be emptied and cannot be refilled within a few days, it is essential, that they are rinsed repeatedly with water and after that be emptied completely. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
You can choose any direction of flow. 7 check the tightness of the coolant circulation. 8 perform a leak test with the required pressure (6 bar). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
EN 50178/VDE 0160, sect. 5.2.16.1. Series BUC64S/A/F power converters are conditional short-circuit-proof in the sense of EN 50178/VDE 0160, sect. 6.3.4. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 46
Touch parts only after you have assured that they are voltage free and after unit and motor have been secured against reactivation. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
ZCable for control voltage supply / signals– on page 100 and ZCable for mains supply to appliance– on page 100. h make sure all cables used meet the requirements. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
6.4.1 Power terminals The power connections are located at the bottom side of the unit (see Zfigure 15– page 48). figure 15: Power terminals Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Assure, that if there are higher current requirements that it is multiple-separately supplied. Make sure, that all applied control voltages meet the PELV or SELV requirements. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Each terminal is to be loaded with a maximum load of 10 A. If you require more current to be conducted, feed by use of 2 termi- nals. This way a total of 20 A is possible. The BUC64S/A/F transmits with this output the “ready-for-use“ to the connected appliance(s). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
18: potential free optocoupler input M Reset Reference potential for +Reset input (M = GND) Position, see Zfigure 17– on page 51. Conductor cross-section. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Phase L1 mains voltage after mains contactor, max. 5 mA Phase L2 mains voltage after mains contactor, max. 5 mA Phase L3 mains voltage after mains contactor, max. 5 mA Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
PLL net synchronous Mains connection at x1:8/9/10 o. k. (without LED display) BUC controller released (without LED display) Ready Ready-for-use BUC power unit Accumulative message of IGrd Imax Uzk> Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
EMVG for your plant) and if the EMC compatibility inside the switching cabinet is guaranteed. (This you can assume, when you have observed all configuration instructions given in this documentation). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Do not interrupt the cable by e.g. terminals, circuit breakers, fuses etc. m The cable (DC link connection) between BUC and the connected BUS units should be kept as short as possible. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
For each unit use a separate mains filter. If you must suppress all drives together - do not interrupt the screening between the converter and the motor. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
(e.g. filtering), may impair the screening effect of these housings. h form a good conductive connection of the cable screens where the cable enters the housing. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Cable tails that are only 3 cm long (1 cm of wire = 10 nH) reduce the screening effect in the megahertz range by up to 30 dB! Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
This means that converters may be incompatible with earth leakage circuit-breakers! h In this context observe the safety information given in the EN 50178/VDE 0160 sect. 5.2.11.2. standard. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Further information you will find in ZBlock switching diagrams– from page 29 and ZCon- nection diagram– from page 60. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Installation figure 27: BUC64S/A/F connection diagram Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 62
+ 24 V 24 V power supply with secure electrical isolation (PELV) according to IEC 61131-2; table 7 for supplying of the electronic section. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
(control-) terminals are routed and connected properly. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
(see Z7.5.1 Step-by-step starting– on page 66) and be aware of faulty or uncontrolled conditions of the plant. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
(axis/axes). The DC-link is loaded to nom- inal voltage and is controlled by the BUC-controller constantly. Settings on the supply-/recovery unit are not necessary. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
DC-link) doesn’t take longer than 120 s. See description of the BUS axes. Switch-on Switch on the device in the prescribed correct order (see ZStep-by-step starting– page 66). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
If the BUC is connected to the attached BUS axes over the signal lines (see ZFigure 27– on page 61), the monitoring functions of the supply unit influence the axes over the line „BBint“ (ready-for-use). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
This signal is evaluated by the devices which are connected to X99A-5 (BBint). The LED „ready“ displays the message „ready-for-use power unit“. The LED „BBint“ displays the message „ready-for-use“ (BBint/BBext). (LED-displays see ZFigure 19– on page 53). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
As a cause of fault an earth fault at the motor con- nection is likely. The message "ready-for-use" (BBint and BBext) is withdrawn. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Page 71
In order to guarantee a recovery of the transistor after a switching-off because of overcurrent, the message can be reset not until after five seconds (typical are 10 s). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a...
71. Figure 30: Pre-warning power unit temperature 8.6.2 PLL synchronous The contact „pre-warning error“ X99AB:3/4 opens, if the supply module is not synchro- nous. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
The specified environmental conditions you will find in chapter ZAppendix D - Technical Specifications– from page 95. h monthly check the mixture ratio of the anticorrosive (applies to window variant F only). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 74
Inspection interval Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Also this has to be written down in a chronological protocol (service note-book). If this is disregarded, the operator runs the risk of liability consequences. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 76
Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Before working at electrical connections check with suitable test instruments that there is no more voltage at the terminals. Only demount connections after you are sure that they are completely powerless. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
1 When having the window variants A/F the sealing strips have to be changed. ZMounting BUC64 window variant A/F– on page 41 2 Carry out commissioning like for a new appliance (see chapter 5 to 8). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
ISPOSAL In this chapter we describe the correct and secure disposal of BUC64 S/A/F-appliances. During the disposal you will get mainly metal parts (iron- and non-iron metal), electronics scrap and plastics. 12.1 Safety regulations The disposal is to be carried out only according to the safety regulations. Observe also particular local regulations.
(D) the plastic parts of the housing, the plastic covers and other small parts made from plastic must be given to the plastics recycling. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Make sure, that the disposal is carried out according to your company’s regulations and the regulations of the disposal companies and official administration. If in doubt, contact the local business administration, environmental office or other. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 82
12.4 Recycling plants / offices Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Page 83
Analog reference potential Digital reference potential EXT, ext External External reference for 24 V con- BEDAS missing troller inputs Fault current Ballast unit Error position encoder signal Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 84
Function module Position Control SELV separated extra low voltage sys- Light-emitting diode Telegram length Following error Function module Power Module Current limit reached Low word Quick stop Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Effective value, direct current volt- “Verband deutscher Elektrotechni- ker“ German electrical engineer con- nected Logic element Voltage, curve form not defined Inverter limit position Terminal strip DC link, intermediate circuit Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 86
Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
450A/1000V: 3NE3 233 size 1 110 mm 450A/1000V: 3NE3 333 size 2 110 mm size NOTE The fuses are not suitable for switch disconnectors. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Accessories Line reactor Water cooler seal tape: part number 00350790 coupling (connection accessory): contact Baumüller Nürnberg GmbH. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 90
Water cooler Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
As all converters and control systems comply with the requirements of the harmonized standards EN50178, EN 60204-1, EN 60529 and HD625.1 S1, the protection targets of 73/23/EWG are reached. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Declaration by Manufacturer to the fact that it is prohibited to put the ma- chine as a whole into operation before it has been declared that the machine conforms to the provisions of the Machinery Directive. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Isolationskoordination für elektrische Betriebsmittel in Niederspannungsanlagen Insulation coordination for equipment within low-voltage systems Nürnberg, 11.01.2005 ________________________ ________________________ Andreas Baumüller ppa. Dr. Peter Heidrich Geschäftsführer Entwicklungsleiter Head Division Head of development Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Baumüller Nürnberg GmbH, Ostendstr. 80 - 90, D- 90482 Nürnberg Nürnberg, 11.01.2005 ________________________ ________________________ Andreas Baumüller ppa. Dr. Peter Heidrich Geschäftsführer Entwicklungsleiter Head Division Head of development Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
The supply voltage must meet the requirements of PELV (EN 50178, chapter 3.49) or SELV (EN 50178, chapter 3.70). EN6 1131-2:1994, table 7 Burst immunity Signal interfaces 1 kV Power interfaces 2 kV Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
40 °C is the rated temperature characteristic curve: power output of appliance in dependence of mounting height at normal pressure EN 50178, chapter 9.4.3.2 EN 50178, table 2 Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Page 97
Ca /l). A pH-value between 6.5 and 7.5 must be kept. Use a closed loop coolant circulation! Air inside and outside switching cabinet. Air inside switching cabinet. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
This power withdrawal is only permitted over short duration (max. 120 s). This has to be assured by accordant parameterization of the connected axes (BUS devices). DC-link (see manual of the BUS devices). Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
IP 00/IP 54 outside Fight fire with ABC-Powder The first value is the depth inside the switching cabinet. The second value is the depth outside the switching cabinet. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Mount max. 2 cable lugs per power rail. Do not mount cable lugs onto each other, mount one on each side of the power rail. Use cable lugs that have a maximum width of 35 mm. Keep in mind that the M10 screw is used for attachment. Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH...
Proposal for the screen connection.................... BUC64S/A/F connection diagram ....................Monitoring functions and „ready-for-use“ ................... Ready-for-use-messages BUC 64 ..................... Pre-warning power unit temperature..................Demounting scheme ........................Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 102
Table of figures Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Environmental temperature unsymmetry First steps Voltage - drop Grounding Guarantee Harmonic oscillation Introduction Low Voltage Directive low voltage supply max. DC link voltage Maximum temperature Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a of 104...
Page 104
Index Manual Feed/Feedback Unit with analog Controller BUC64 S/A/F Document no.: 5.02024.03a Baumüller Nürnberg GmbH of 104...
Page 106
Baumüller Nürnberg GmbH Ostendstraße 80-90 90482 Nürnberg T: +49(0)911-5432-0 F: +49(0)911-5432-130 www.baumueller.de All information given in this manual is customer information, subject to change without notice. We reserve the right to futher develop and actualize our products continuously using our permanent revision service. Please notice, that specifications/data/information are current values according to the printing date. These statements are not legally binding according to the measurement, computation and calculations.
Need help?
Do you have a question about the BUC64 S and is the answer not in the manual?
Questions and answers