Automatic restart (SAF-001-000-002 and SAF-001-001-xxx)

8.13 Automatic restart (SAF-001-000-002 and SAF-001-001-xxx)
The safety module SAF-001 is available in the version SAF-001-000-002 and
SAF-001-001-xxx with automatic restart. The connection of a restart switch is not
necessary here.
The pulse inhibit for the drive is deactivated from the module immediately after reset of
STO. The restart of the drive depends only on the operating state of the controller. Thus,
the restart is no part of the safety function.
58
Operation Manual Safety Module for b maXX 5000 BM5-O-SAF-000/-001
Document no.: 5.09013.07
of 114
DANGER!
The safety function STO is already canceled by resetting the safety component which
has triggered the function STO. From that point on, the machine can be restarted in
case of a failure even if the restart input is deactivated.
NOTICE!
If a restart inhibit is necessary in the application, the SAF-001-000-000 module
should be used. If the module version SAF-001-000-002 or SAF-001-001-xxx is
used, the restart inhibit must be realized externally.
DANGER!
The safety function STO is already canceled by resetting the safety component which
has triggered the function STO. From that point on, the machine can be restarted.