8.2

Compatibility list

fixed SS1 time of 200 ms the drive is switched off by a safe pulse inhibit. After that the
module is in the STO state (safe torque off).
Safe Stop 1 (SS1) with time control:
m When using the safety function SS1 the control of the power output stage is safely
m The safety function SS1 corresponds to Stop Category 1 of EN 60204-1.
8.2
Compatibility list
8.2.1

Compatibility list SAF-001-000-xxx

The Safety Module (SAF-001-000-xxx) can only be operated in combination with
converters of the type b maXX 5000 released by the company Baumüller Nürnberg
GmbH.
If the converter was previously equipped with a module with a higher safety level
(SAF-002/003), the parameter storage of the converter must be reset with the Reset-
Module.
8.2.2

Compatibility list SAF-001-001-xxx

The Safety Module (SAF-001-001-xxx) with automatic restart can only be operated in
combination with converters of the type b maXX 5000 with firmware version V01.10.02 or
higher by the company Baumüller Nürnberg GmbH. A firmware version V01.14.00 or
higher must be used for the Safety Module with SS1 function (SAF-001-001-001).
If the converter was previously equipped with a module with a higher safety level
(SAF-001 without automatic restart, SAF-002 or SAF-003), the parameter storage of the
converter must be reset with the Reset-Module or with the reset command (see
ZOperation mode of the reset command–
If the converter was previously equipped with a module which includes a STO function
(SAF-001-000-xxx, SAF-001-001-000) and is equipped with the module STO 001-001-
001 (SS1 function), the safety level of the converter must be reset to zero by the Reset
module or by the Reset command (see
page 65).
WARNING!
A converter b maXX 5000 with a firmware version V01.14.00 or higher must be used
for the Safety Module with SS1 function (SAF-001-001-001).
38
Operation Manual Safety Module for b maXX 5000 BM5-O-SAF-000/-001
Document no.: 5.09013.07
of 114
interrupted after a delay time of 200 ms. The drive can be braked to a standstill by the
drive control within the SS1 time if appropriate parameterizations were made in the
controller (see Working Principle
ZSAF-001-001-xxx–
on page 40).
on page 65).
ZOperation mode of the reset command–
Baumüller Nürnberg GmbH
on