10.1 General
For the operation of an axis unit of the series b maXX 5000, the slot A of the device must
be equipped with a module (also see 5.09021, Instruction handbook b maXX 5000). In
case the device was already equipped with a module of a higher safety level, the safety
level of the converter can be reset without a Reset-Module with a controller command
also.
10.2 Operation mode of the reset command
The safety level of the converter is reset to the value zero by the command. The
parameter files remain in the converter.
The following mode of operation for resetting must be followed:
1 Writing of the value 4096 into parameter 139.023.0.0 (system command)
2 On the 7-segment-display a four-digit code is displayed after the prefix „C"
3 This code must be written in parameter 200.020.0.0 (reset code).
4 After 15 seconds the voltage supply can be switched off and slot A can be equipped
Operation Manual Safety Module for b maXX 5000 BM5-O-SAF-000/-001
R
ESETTING OF THE SAFETY LEVEL
10
with the required module.
BY THE CONTROLLER
Document no.: 5.09013.07
65
of 114