4.2 General Specifications

Mains supply
Supply Terminals (6-Pulse)
Supply Terminals (12-Pulse)
Supply voltage
Supply voltage
Supply voltage
4
4
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
Switching on input supply L1, L2, L3 (power-ups) ≥ 90 kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
Motor output (U, V, W)
Output voltage
Output frequency (0.25-75 kW)
Output frequency in Flux Mode
Switching on output
Ramp times
1)
Voltage and power dependent
Torque characteristics
Starting torque (constant torque)
Starting/overload torque (variable torque)
Torque rise time in FLUX (for 5 kHz fsw)
Torque rise time in VVC
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
72
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
plus
(independent of fsw)
2)
2)
MG33BE02 - VLT
FC 301: 380-480 V/FC 302: 380-500 V ±10%
overvoltage category III/pollution degree 2
maximum 160% for 60 s
maximum 110% up to 0.5 s
®
is a registered Danfoss trademark
L1, L2, L3
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
200-240 V ±10%
FC 302: 525-600 V ±10%
FC 302: 525-690 V ±10%
50/60 Hz ±5%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
maximum 2 times/min.
maximum 1 time/min.
maximum 1 time/2 min.
0-100% of supply voltage
0-590 Hz
0-300 Hz
Unlimited
0.01-3600 s
1)
once in 10 min.
1)
once in 10 min.
1 ms
10 ms
FC 301: 4 (5)
1)
/FC 302: 4 (6)
1)
1)
18, 19, 27
, 29
, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0-110 kHz