This section describes codes which can be used in the
function and data fields of a Modbus RTU message.
10.10.10 Function Codes Supported by
Modbus RTU
Modbus RTU supports use of the following function codes
in the function field of a message.
Function
Read coils
Read holding registers
Write single coil
Write single register
Write multiple coils
Write multiple registers
Get comm. event counter
Report slave ID
Table 10.17 Function Codes
Function
Function
Sub-
Code
function
code
Diagnostics
8
1
2
10
11
12
13
14
Table 10.18 Function Codes

10.10.11 Modbus Exception Codes

For a full explanation of the structure of an exception code
response, refer to 10.10.5 Function Field.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
Function Code
1 hex
3 hex
5 hex
6 hex
F hex
10 hex
B hex
11 hex
Sub-function
Restart communication
Return diagnostic register
Clear counters and
diagnostic register
Return bus message count
Return bus communi-
cation error count
Return bus exception error
count
Return slave message
count
®
MG33BE02 - VLT
is a registered Danfoss trademark
Code Name
Meaning
1
Illegal
The function code received in the query is
function
not an allowable action for the server (or
slave). This may be because the function
code is only applicable to newer devices,
and was not implemented in the unit
selected. It could also indicate that the
server (or slave) is in the wrong state to
process a request of this type, for
example because it is not configured and
is being asked to return register values.
2
Illegal data
The data address received in the query is
address
not an allowable address for the server
(or slave). More specifically, the
combination of reference number and
transfer length is invalid. For a controller
with 100 registers, a request with offset
96 and length 4 would succeed, a request
with offset 96 and length 5 generates
exception 02.
3
Illegal data
A value contained in the query data field
value
is not an allowable value for server (or
slave). This indicates a fault in the
structure of the remainder of a complex
request, such as that the implied length is
incorrect. It specifically does NOT mean
that a data item submitted for storage in
a register has a value outside the
expectation of the application program,
since the Modbus protocol is unaware of
the significance of any particular value of
any particular register.
4
Slave device
An unrecoverable error occurred while the
failure
server (or slave) was attempting to
perform the requested action.
Table 10.19 Modbus Exception Codes

10.11 How to Access Parameters

10.11.1 Parameter Handling

The PNU (Parameter Number) is translated from the
register address contained in the Modbus read or write
message. The parameter number is translated to Modbus
as (10 x parameter number) DECIMAL.

10.11.2 Storage of Data

The Coil 65 decimal determines whether data written to
the frequency converter are stored in EEPROM and RAM
(coil 65=1) or only in RAM (coil 65= 0).