Danfoss VLT AutomationDrive FC 300 Design Manual page 101

0.25-75 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

How to Order
FC 302
Frequency converter data
Mains
P
R
m
min
[type]
[kW]
[Ohm]
T7
4
180
T7
5,5
130
T7
7,5
94
T7
11
69,7
T7
15
46,8
T7
18,5
36,0
T7
22
33,7
T7
30
22,5
T7
37
18,0
T7
45
13,5
T7
55
13,5
T7
75
8,8
T7
90
8,8
Table 5.11 FC 302 Vertical Braking
Horizontal braking: duty cycle 10% and maximum 120 s repetition rates according the reference brake profile. Average power corresponds to 6%.
Vertical braking: duty cycle 40% and maximum 120 s repetition rates according the reference brake profile. Average power corresponds to 27%.
Cable cross section: recommended minimum value based upon PVC insulated copper cable, 30 °C ambient temperature with normal heat
dissipation.
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (60/75°C) conductors are
recommended.
Thermal relay: Brake current setting of external thermal relay. All resistors has a build-in thermal relay switch N.C.
IP54: flat pack type with 1000 mm fixed unscreened cable. Vertical and horizontal mounting. Derating required by horizontal mounting.
IP21 & IP65: with screw terminal for cable termination. Vertical and horizontal mounting. Derating required by horizontal mounting.
IP20: with screw terminal for cable termination. Floor mounting.
P
: Frequency converter nominal output power as HO.
m
R
: Minimum permissible brake resistor value by frequency converter.
min
R
is the nominal resistor value that ensure a brake power on motor shaft of 150%/160% for 1 minute.
br,nom
R
: resistor value and resistance of the brake resistor.
rec
P
: Power rating of the brake the brake resistor as the average power during continuous braking.
br,cont
150/160%
0 0.8
3
Illustration 5.1 Horizontal reference brake profile
* Maximum 120 s repetition rates with equal average power or duty cycle.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
R
,nom
R
P
,cont.
br
rec
br
[Ohm]
[Ohm]
[kW]
216
200
1,700
156
145
2,200
113
105
3,200
76,2
72
4,200
55,5
52
6,000
44,7
42
8,000
37,5
31
10,000
29,1
27
14,000
23,5
22
17,000
19,3
15,5
21,000
15,7
13,5
26,000
11,5
11
36,000
9,5
9,1
42,000
30* [s]
®
MG33BE02 - VLT
is a registered Danfoss trademark
Vertical braking
Brake Resistor data
Ordering no.
Screw
Screw
Wire IP54
Terminal
Terminal
IP21
IP65
[p/n]
[p/n]
[p/n]
x
175u3122 175u3123
x
175u3106 175u3107
x
175u3132 175u3133
x
175u3142 175u3143
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
150/160%
100%
0
Illustration 5.2 Vertical reference brake profile
Installation
Cable
Thermal
Screw
Cross
relay
Terminal
section
IP20
[p/n]
2
[A]
[mm
]
x
1,5
2,8
x
1,5
3,7
x
1,5
5,2
x
1,5
7,2
175u3242
2,5
10,8
175u3243
2,5
13,9
175u3244
4
18
175u3201
10
22,8
175u3202
10
27,8
175u3205
16
36,9
175u3209
16
43,9
175u3212
25
57,3
175u3214
35
68
30* [s]
10.5
12
5
5
99

Advertisement

Table of Contents
loading

Table of Contents