How to Order
FC 302
P
m
T5
[kW]
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
Table 5.15 FC 302 Mains: 380-500 V (T5)
IP65: flat pack type with fixed cable.
P
: Frequency converter nominal output power as HO.
m
R
: Minimum permissible brake resistor value by frequency converter.
min
R
is the nominal resistor value that ensure a brake power on motor shaft of 150%/160% for 1 minute.
br,nom
R
: resistor value and resistance of the brake resistor.
rec
Duty cycle: resulting duty cycle based on resistor power and frequency converter data.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
R
R
min
br. nom
[Ω]
[Ω]
620
1389
620
929
558
678
620/100 or 620/200
382
453
430/100 or 430/200
260.0
325.9
189.0
218.6
135.0
158.5
150/200 or 300/200
99
117
72
84
50
61
36.0
41.2
27.0
30.0
®
MG33BE02 - VLT
is a registered Danfoss trademark
Flatpack IP65 for horizontal conveyors
R
per item
Duty Cycle
rec
[Ω/W]
%
830/100
30
830/100
20
14 or 27
10 or 20
310/200
14
210/200
10
7 or 14
240/200
10
160/200
8
130/200
6
80/240
5
72/240
4
Ordering no.
175Uxxxx
1000
1000
1001 or 0982
1002 or 0983
0984
0987
0989 or 2 x 0985
5
2 x 0986
2 x 0988
2 x 0990
2 x 0090
2 x 0091
101
5