RS-485 Installation and Set...
Coil
Description
Number
1-16
Frequency converter control word
(see )
17-32
Frequency converter speed or set-
point reference Range 0x0 – 0xFFFF
(-200% ... ~200%)
33-48
Frequency converter status word
(see Table 10.16)
49-64
Open loop mode: Frequency
converter output frequency Closed
loop mode: Frequency converter
feedback signal
65
Parameter write control (master to
slave)
0
=
1
=
66-6553
Reserved
6
Table 10.13 Coil Descriptions
Coil
0
10
10
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
04
Coast stop
05
Quick stop
06
Freeze freq.
07
Ramp stop
08
No reset
09
No jog
10
Ramp 1
11
Data not valid
12
Relay 1 off
13
Relay 2 off
14
Set up LSB
15
Set up MSB
16
No reversing
Table 10.14 Frequency Converter Control Word (FC Profile)
* Used to specify the index number to be used when accessing an indexed parameter.
190
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
Parameter changes are written to
the RAM of the frequency
converter
Parameter changes are written to
the RAM and EEPROM of the
frequency converter.
1
No DC brake
No coast stop
No quick stop
No freeze freq.
Start
Reset
Jog
Ramp 2
Data valid
Relay 1 on
Relay 2 on
Reversing
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
Signal Direction
Coil
33
Master to slave
34
Master to slave
35
36
37
Slave to master
38
39
Slave to master
40
41
42
43
Master to slave
44
45
46
47
48
Table 10.15 Frequency Converter Status Word (FC Profile)
Register
Number
00001-00006
00007
00008
00009
00010-00990
01000-01990
02000-02990
03000-03990
04000-04990
...
49000-49990
50000
50010
...
50200
50210
Table 10.16 Holding Registers
®
MG33BE02 - VLT
is a registered Danfoss trademark
0
1
Control not ready
Control ready
Frequency converter not
Frequency converter ready
ready
Coasting stop
Safety closed
No alarm
Alarm
Not used
Not used
Not used
Not used
Not used
Not used
No warning
Warning
Not at reference
At reference
Hand mode
Auto mode
Out of freq. range
In frequency range
Stopped
Running
Not used
Not used
No voltage warning
Voltage warning
Not in current limit
Current limit
No thermal warning
Thermal warning
Description
Reserved
Last error code from an FC data object interface
Reserved
Parameter index*
000 parameter group (parameters 001 through
099)
100 parameter group (parameters 100 through
199)
200 parameter group (parameters 200 through
299)
300 parameter group (parameters 300 through
399)
400 parameter group (parameters 400 through
499)
...
4900 parameter group (parameters 4900 through
4999)
Input data: Frequency converter control word
register (CTW).
Input data: Bus reference register (REF).
...
Output data: Frequency converter status word
register (STW).
Output data: Frequency converter main actual
value register (MAV).