8 General Specifications

Line power supply (L1, L2, L3):
Supply voltage
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage drops below the minimum
stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage. Power-up and full torque cannot be
expected at AC line voltage lower than 10% below the adjustable frequency drive's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between line phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
THiD
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480/690 V maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Ramp times
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to the nominal torque of the adjustable frequency drive.
Cable lengths and cross-sections:
Max. motor cable length, shielded/armored
Max. motor cable length, unshielded/unarmored
Max. cross-section to motor, line power, load sharing and brake *
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
* See Line Power Supply tables for more information!
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
®
MG.16.A1.22 - VLT
is a registered Danfoss trademark
8 General Specifications
3.0% of rated supply voltage
> 0.98 nominal at rated load
overvoltage category III / pollution degree 2
0–100% of supply voltage
maximum 110% for 1 min.
maximum 135% up to 0.5 sec.
maximum 110% for 1 min.
0.0023 in
2
[1.5 mm
2
]/16 AWG (2 x 0.00112
0.0016 in
0.0008 in
18, 19, 27
380–480 V +5%
50/60 Hz ±5%
(> 0.98)
< 5%
maximum once/2 min.
0–800* Hz
Unlimited
1–3600 sec.
8
*
*
*
492 ft [150 m]
984 ft [300 m]
2
in [0.75 mm
2
])
2
[1 mm
2
]/18 AWG
2
[0.5 mm
2
]/20 AWG
2
2
0.039 in
[0.25 mm
]
4 (6)
1)
, 29
1)
, 32, 33,
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
approx. 4 kΩ
8-1