Danfoss VLT AutomationDrive FC 300 Design Manual page 127

0.25-75 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Electrical Installation
Enclosure
Power [kW]
size
A2
0-75-4.0
A3
5.5-7.5
B3
11-15
B4
18.5-30
C3
37-45
C4
55-75
A5
0.75-7.5
B1
11-18
B2
22-30
C1
37-55
C2
75
Table 7.21 525-600 V, Frame Sizes A, B and C
Enclosure
Power [kW]
size
A3
1.1
1.5
2.2
3
4
5.5
7.5
B2
11
15
18
22
C2
30
37
45
55
75
C3
37
45
Table 7.22 525-690 V, Frame Sizes A, B and C
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
Recommended
Recommended
fuse size
gG-10
gG-10 (5.5)
gG-16 (7.5)
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-63 (37)
gG-100 (45)
aR-160 (55)
aR-200 (75)
gG-10 (0.75-5.5)
gG-16 (7.5)
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-63 (37)
gG-160 (37-45)
gG-100 (45)
aR-250 (55)
aR-160 (55)
aR-200 (75)
Recommended
Recommended
fuse size
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 (30)
gG-80 (30)
gG-63 (37)
gG-100 (37)
gG-80 (45)
gG-125 (45)
gG-100 (55)
gG-160 (55-75)
gG-125 (75)
gG-80
gG-100
®
MG33BE02 - VLT
is a registered Danfoss trademark
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-150
NZMB2-A200
aR-250
NZMB2-A250
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
aR-250
NZMB2-A250
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
-
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-63
-
-
gG-100
-
gG-125
Max trip level [A]
25
25
50
100
150
250
25
7
63
100
160
250
Max trip level [A]
-
-
-
-
125
7

Advertisement

Table of Contents
loading

Table of Contents