FC 300 Selection
(Duty cycle) Min. pulse width
Input resistance, R
i
3, 4)
Safe stop Terminal 37
(Terminal 37 is fixed PNP logic)
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Maximum voltage on input
Typical input current at 24 V
Typical input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1)
Terminals 27 and 29 can also be programmed as output.
2)
Except safe stop input Terminal 37.
3)
See 3.12 Safe Stop for further information about terminal 37 and Safe Stop.
4)
When using a contactor with a DC coil inside in combination with Safe Stop, it is important to make a return way for the
current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for
quicker response time) across the coil. Typical contactors can be bought with this diode.
Analog inputs
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
i
Max. voltage
Current mode
Current level
Input resistance, R
i
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Illustration 4.1 PELV Isolation
Pulse/encoder inputs
Programmable pulse/encoder inputs
Terminal number pulse/encoder
Max. frequency at terminal 29, 32, 33
Max. frequency at terminal 29, 32, 33
Min. frequency at terminal 29, 32, 33
Voltage level
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
PELV isolation
+24V
Control
18
High
voltage
37
Functional
isolation
RS485
®
MG33BE02 - VLT
is a registered Danfoss trademark
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
-10 to +10 V (scaleable)
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scaleable)
Max. error 0.5% of full scale
Mains
Motor
DC-Bus
1)
29
, 33
110 kHz (Push-pull driven)
5 kHz (open collector)
see section on Digital input
4.5 ms
approx. 4 kΩ
0-24 V DC
<4 V DC
>20 V DC
28 V DC
50 mA rms
4
4
60 mA rms
400 nF
2
53, 54
approx. 10 kΩ
± 20 V
approx. 200 Ω
30 mA
10 bit (+ sign)
100 Hz
2/1
2)
3)
3)
/ 32
, 33
4 Hz
73