FC 300 Selection
Control card, USB serial communication
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection earth. Use only an isolated laptop as PC connection to
the USB connector on the frequency converter.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
1)
Max. terminal load (AC-1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
(Inductive load)
Relay 02 (FC 302 only) Terminal number
1)
Max. terminal load (AC-1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (AC-15)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 4-5 (NO) (Resistive load)
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
1)
Max. terminal load (AC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (AC-15)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300 V AC2A
Cable lengths and cross sections for control cables
Max. motor cable length, screened
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
1)
For power cables, see 4.1 Electrical Data - 200-240 V.
Control card performance
Scan interval
Control characteristics
Resolution of output frequency at 0-590 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19)
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open loop)
Speed control range (closed loop)
Speed accuracy (open loop)
Speed accuracy (closed loop), depending on resolution of feedback device
Torque control accuracy (speed feedback)
All control characteristics are based on a 4-pole asynchronous motor
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
2)3)
Overvoltage cat. II
1)
®
MG33BE02 - VLT
is a registered Danfoss trademark
1.1 (Full speed)
USB type B "device" plug
FC 301 all kW: 1/FC 302 all kW: 2
1-3 (break), 1-2 (make)
240 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24 V AC 20 mA
overvoltage category III/pollution degree 2
1.5 mm
1 mm
0.5 mm
0.25 mm
1:100 of synchronous speed
1:1000 of synchronous speed
30-4000 rpm: error ±8 rpm
0-6000 rpm: error ±0.15 rpm
max error ±5% of rated torque
4
4
60 V DC, 1 A
80 V DC, 2 A
50 V DC, 2 A
150 m
300 m
2
/16 AWG
2
/18 AWG
2
/20 AWG
2
/24 AWG
1 ms
±0.003 Hz
≤±0.1 ms
≤ 2 ms
75