RS-485 Installation and Set...
10 RS-485 Installation and Set-up

10.1 Installation and Set-up

10.1.1 Overview

RS-485 is a two-wire bus interface compatible with multi-
drop network topology, that is, nodes can be connected as
a bus, or via drop cables from a common trunk line. A
total of 32 nodes can be connected to one network
segment.
Repeaters divide network segments.
NOTE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address, across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use screened
twisted pair (STP) cable for bus cabling, and always follow
good common installation practice.
Low-impedance earth connection of the screen at every
node is important, including at high frequencies. Thus,
connect a large surface of the screen to earth, for example
with a cable clamp or a conductive cable gland. It may be
necessary to apply potential-equalizing cables to maintain
the same earth potential throughout the network - partic-
ularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable
Screened twisted pair (STP)
120 Ω
Impedance
Max. 1200 m (including drop lines)
Cable length
Max. 500 m station-to-station
Table 10.1 Cable

10.2 Network Connection

One or more frequency converters can be connected to a
control (or master) using the RS-485 standardized interface.
Terminal 68 is connected to the P signal (TX+, RX+), while
terminal 69 is connected to the N signal (TX-,RX-). See
drawings in 7.8.3 Earthing of Screened Control Cables.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx
®
VLT
AutomationDrive FC 300 Design Guide, 0.25-75 kW
If more than one frequency converter is connected to a
master, use parallel connections.
Illustration 10.1 Parallel Connections
In order to avoid potential equalizing currents in the
screen, earth the cable screen via terminal 61, which is
connected to the frame via an RC-link.
Illustration 10.2 Control Card Terminals

10.3 Bus Termination

The RS-485 bus must be terminated by a resistor network
at both ends. For this purpose, set switch S801 on the
control card for "ON".
For more information, see 7.5.4 Switches S201, S202, and
S801 .
Communication protocol must be set to 8-30 Protocol.
®
MG33BE02 - VLT
is a registered Danfoss trademark
RS 232
68
+
USB
-
RS 485
61 68 69
39 42 50 53 54 55
Remove jumper to enable Safe Stop
12
13
18
19
27
29
69
68
69
68
69
10
32
33
20
37
181