Appendix C: Sia Event Structure - Honeywell Galaxy Flex Installer Manual

Hide thumbs Also See for Galaxy Flex:
Table of Contents

Advertisement

Galaxy Flex Installer Manual

Appendix C: SIA event structure

Event
SIA
ACC.
Type
Level
Block
Zone
3,4
#xxxxxx
2
#xxxxxx
1
#xxxxxx
0
#xxxx
User
3,4
#xxxxxx
2
#xxxxxx
1
#xxxxxx
0
#xxxx
Module
3,4
#xxxxxx
2
#xxxxxx
1
#xxxxxx
0
#xxxx
Event
3,4
#xxxxxx
2
#xxxxxx
1
#xxxxxx
0
#xxxx
Key
Data Block
Time modifier
ti
Group modifier (not used if groups are
ri
disabled)
User modifier
id
User number
u
Peripheral modifier
pi
Peripheral number
m
Event Code Type (see SIA event list
EV
supplied)
Zone number
z
maximum digits for modifier field
x
DATA Block Format
(N block code)
Ntixx:xx/rixx/EVzzzz
Ntixx:xx/rixx/EVzzzz
NEVzzzz
NEVzzzz
Ntixx:xx/rixx/iduuu/pixxx/EV
Ntixx:xx/rixx/iduuu/pixxx/EV
NEVmmm
NEVmmm
Ntixx:xx/rixx/pimmm/EV
Ntixx:xx/rixx/pimmm/EV
NEVmmm
NEVmmm
Ntixx:xx/rixx/EV
Ntixx:xx/rixx/EV
NEV
NEV000
Appendix C: SIA event structure
Ascii Block Format
(A block code)
Aeeeeeeeeesiiiiiiii
dddddddddddddddd
Aeeeeeeeeesiiiiiiii
dddddd
Aeeeeeeeeesiiiiiiii
ddd
Aeeeeeeeeesiiiiiiii
Ascii Block
Log event (9 chars, see Log Event in table
e
supplied)
Event state ('+' : ON, '-' : OFF, ' ' : NOT
s
USED)
Site identifier (8 char description of site - can
I
be blank)
Descriptor (additional text to describe event),
d
1. Zone Event - 16 character zone descriptor
2. User Event - 6 character user name
3. Module Event - 3 character module name,
'RIO' (8 zone module), 'KEY' (keypad), 'MAX'
(Proximity Reader), 'COM'
(COM1 = Int Telecom, COM3 = ISDN,
COM4 = Ethernet, COM5 = GSM/GPRS,
COM6 = USB)
Explanation
Detector alarmed,
keyswitch etc
User Set/Unset, reset,
duress, etc
1. With ri modifier:
Set with A or B key
without code
2. Without ri modifier:
Keypad added, Rio
missing etc
1. With ri modifier:
Automatic set, timer
activated
2. Without ri modifier:
Automatic test, engineer
mode