Honeywell Galaxy Flex Installer Manual page 181

Hide thumbs Also See for Galaxy Flex:
Table of Contents

Advertisement

Galaxy Flex Installer Manual
MAX Parameters [69.2.2]
Use this option to define the operational features of each MAX module. When you select
this option the address of the first MAX on the system is displayed along with the descriptor
currently assigned to it. At the same time LEDs on the MAX module display the address in a
pattern format. Press
pattern on the MAX module. For more information see Reader [25.3] on page 44.
Descriptor [69.2.2.1]
Use this to assign a name of up to 12 characters to each of the MAX modules.
Relay Duration [69.2.2.2]
After a user card swipe, this is the time allowed to open a door without creating an alarm.
The MAX relay de-activates as soon as the door contact opens or the Open Timeout occurs.
The range is 01 to 60 seconds, and the default time is 5 seconds.
Press
or
to increase or decrease the time in one second increments.
A
B
Open Timeout [69.2.2.3]
This is the time a door can remain open after a card swipe. If the door remains open longer
than the period assigned to the Open Timeout, then an alarm occurs.
Note: If the Open Timeout is programmed as 0 seconds, then the door can remain open
indefinitely without resulting in an alarm being activated.
The range is 00 to 60 seconds, and the default time is 10 seconds.
Press
or
to increase or decrease the time in one second increments.
A
B
Alarm Group [69.2.2.4.1]
When you select the Alarm Group option, the group currently allocated to the MAX is
displayed. Press the group number to toggle the group assigned to the MAX. The MAX does
not allow access through the door when the group is set. A user must have this group
assigned to them in order to gain access at this door.
Multi-group Systems
When the required groups have been assigned to the user, press
programming.
Group Restrict [69.2.2.4.2]
Use this option to assign selected groups to each MAX module. Group restriction affects the
operation of the MAX readers for card held functions. A card can only be used at a reader if
there are common groups between them. By default each reader is assigned to all groups on
the system. Groups can be removed as required to restrict the operation of the MAX reader.
to display a graphic on the keypad that corresponds to the LED
#
Access Control [69]
to accept the
ent
181