Honeywell Galaxy Flex Installer Manual page 81

Hide thumbs Also See for Galaxy Flex:
Table of Contents

Advertisement

Galaxy Flex Installer Manual
Either the engineer or remote user code can select the Secure Code parameter. On selecting
this parameter the secure code equivalent to the current engineer code must be entered to
confirm the selection. Only the remote user code (or a cold start - erasing all programming
details) can cancel it. The default is 0 (disabled).
Fail to Set [51.35]
Use this option to set the period of time that a zone must remain open following the start of
the setting procedure and before the Fail Set outputs activate.
The default is 360 seconds and the range is 0 to 999 seconds.
Notes:
1.
The Fail to Set countdown time begins as soon as the setting procedure is started.
2.
The Fail to Set time should be at a minimum 5 seconds longer than the Exit Time
(option 51.04), to allow for the setting period to expire.
You can assign a different value to each group.
Weekend Work [51.41]
Use this parameter to enable or disable the Weekend Work [45.5] option. If the parameter
is set to 0 (disabled – default setting), the message Option not available is displayed on
selecting Weekend Work [45.5].
Timer Access [51.43]
If enabled a type 6 user can change all the Weekly Schedule information (name, status,
events, holiday period, holiday schedule and pattern day) with the Timers [45.3] option.
If disabled, users can change the Weekly Schedule status only with the Timers [45.3]
option.
Resistance Select [51.46]
RIOs rev 1.2 and Smart PSUs rev 0.7 and above allow zones to be programmed with
different resistance preset values for zone status activation. You can select end-of-line or
double-balanced zone resistance types. Onboard zones can also be modified.
The system default value is 1k fault, double balanced. There are 14 preset resistance
configurations covering both double-balanced and end-of-line.
Parameters [51]
81