15 PA Delay
The PA Delay function is identical to the PA function, with the exception that the PA output
activation can be delayed for up to 60 seconds and is set with the PA Delay [51.13] option.
During the period of delay the entry/exit horns activate to remind the user that the PA Delay
is counting down. Entering a valid code or closing the PA Delay zone aborts the alarm.
Note: If a PA Delay zone is open, it is indicated on the keypad whenever a valid code is
entered. The group that the open PA Delay is assigned to cannot be set until it is
closed.
16 PA Delay Silent
The PA Delay Silent function is identical to the PA Delay function, with the exception that
there is no audible or visible indication of the activation; that is, no bells or strobes are
activated. Only the PA output (normally channel 2 on the digital communicator) signals the
alarm. The activation (+) and restoral (–) of PA Delay Silent zones are recorded in the event
log.
Note: At the time of setting, any PA Delay Silent zones that are currently open are
reported to the user.
18 Spare
The Spare function allows any unused zones to be ignored. The resistance readings from the
circuit, including the tamper conditions, do not activate an alarm condition.
Note: We recommend that all unused zones are programmed as Spare and that a 1 k 1%
resistor is connected across each of these zones.
19 Fire
The Fire function is continuously operational. When activated, a Fire zone overrides the Bell
Delay parameter and activates an instant alarm (Bell, Strobe and Fire). The keypad buzzer
and control panel horn output, if fitted, emit an interrupted tone (one second on, 0.5 seconds
off), easily distinguishable from all other alarm conditions. Any valid code entry cancels the
Fire activation.
20 Tamper
The Tamper function is continuously operational. When a Tamper zone is activated (1 k to
2 k ), a tamper alarm is generated. A Tamper Reset authorized code is required to reset the
alarm (refer to Tamper Reset [51.7]). If a tamper condition (open or short circuit) occurs, a
tamper alarm is also generated.
22 Beam Pair
This function is only operational when two consecutively addressed zones, programmed as
Beam Pair, are open in the set condition. Activation is identical to the Intruder function.
The system cannot set if a single Beam Pair is open.
Note: Beam Pair zones must be consecutively addressed. For example, valid Beam Pair
addresses are 1036 and 1037.
Program Zones [52]
99