Access Control [69]
Use
or
to move the alphabet left or right until the required character is positioned
A
B
underneath the flashing cursor. When the required character is in position press
to copy
ent
the character to the description in the top line. Repeat this procedure to assemble the
required Descriptor.
DCM Reader Relay Duration [69.3.1.5.02]
After a user card swipe, this is the time allowed to open a door without creating an alarm.
The reader relay de-activates as soon as the door contact opens or the Open Timeout occurs.
When you enter this option, the current value is displayed. Assign a time in the range 0 to 60
seconds, the default time is 5 seconds. Press
to save the programming and return to the
ent
previous menu level.
Note: Press
or
to increase or decrease the time in one second increments.
A
B
DCM Reader Open Timeout [69.3.1.5.03]
This is the time a door can remain open after a card swipe. If the door remains open longer
than the period assigned to the Open Timeout an alarm occurs.
Note: If the Open Timeout is programmed as 0 seconds, then the door can remain open
indefinitely without resulting in an alarm being activated.
The range is 0 to 60 seconds, and the default time is 10 seconds.
Press
or
to increase or decrease the time in one second increments.
A
B
DCM Reader Alarm Group [69.3.1.5.04.1]
When you select this option, the group currently allocated to the DCM reader is displayed.
Press the group number to toggle the group assigned to the reader. The reader does not allow
access through the door when the group is set. A user must have this group assigned in order
to gain access at this door.
DCM Reader Group Restrict [69.3.1.5.04.2]
Use this option to assign selected groups to each DCM reader. This group restriction affects
the operation of the DCM readers for both access and card held functions. A card can only
be used at a reader if there are common groups between them. By default each reader is
assigned to all groups on the system. Groups can be removed as required to restrict the
operation of the DCM reader.