Timers [65]
emitted and Prewarn activates at the Autoset time. At the end of the pre-warning period, the
system begins the timed setting procedure.
Note: Pressing
esc
count down. If more than one group is in the pre-warning period, each group can be
viewed by pressing
Extension [65.3.3]
0 – 400 minutes (default 30 minutes):
An autoset Extension can be assigned to each group on the system - programmed with
different values per group. Entering a user code during the Prewarning delays the autosetting
by the period assigned to the Extension.
Note: The Late Working option (refer to Timers [45]) authorizes an Extension in advance
of the pre-warning period.
Late Set appears if the system is not set after Prewarn time plus 300 seconds (longest
possible exit delay). An Extension cannot be granted once the timed setting procedure
begins.
Force Set [65.3.4]
0=Off (default), 1=On
As a factory preset, any zone that is open at the start of the setting procedure - except Final,
Exit, Entry, or Push Set, (or Secure Final or Part Final when acting as a Final) - is omitted
by the autoset routine whether or not it is omittable. If one of the above listed zones is open
and is non-omittable, on expiry of the time programmed in the Fail-to-Set parameter the
Fail-to-Set outputs are activated along with a full alarm.
Autoset Weekly Schedule [65.3.5]
Use this option to assign a programmed weekly schedule to each group when the selected
group is automatically switched On (Autoset) and Off (Autounset).
When the keyswitch is activated twice during the exit time of an autoset, the autoset is
temporarily cancelled for a few seconds, then it restarts the exit time causing the panel to
reset.
Operating a keyswitch zone type during the pre-warn period of an autoset will start a Force
Set. If you then activate the switch again (i.e. unset with keyswitch) before the panel sets,
the pre-warn continues on the autoset.
Note: When the keyswitch is activated the second time to take the panel back into pre-
warn, it can be up to 10 seconds before the pre-warn tones at the keypad start up
again.
174
at any time during the pre-warning resets and restarts the pre-warning
and
or
A
Galaxy Flex Installer Manual
and
.
B