Testing The Configuration - Siemens Sirius 3RK3 System Manual

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Operator control
7.3 Planning/configuring
7.3.3

Testing the configuration

Before you can switch the MSS to safety mode, you must carry out a full function test of the
configuration and then release the configuration.
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
Carrying out a function test of the configuration
A configuration can only be released if a complete function test of the configuration has
been successfully completed (hardware configuration and parameterization of the safety
functions).
Project printouts for the test
Use the printouts of the project to support the test.
Step
Action
1
Open the parameter file containing the configuration that
you have downloaded to the MSS.
2
Activate "Target system" > "Prepare configuration test".
3
Set the interface via which you have access to the device
(e.g. COM1) and confirm with "OK".
● The printout contains all the configuration data stored in the safety relay.
● The configuration CRC is given on each page of the printout in the tabular footer. The
printout is thus always uniquely assigned to one configuration and can later be used for
the plant documentation.
● If deviations or errors occur in these checks, test the configuration and wiring and start
commissioning again.
Switching to test mode
The MSS can be switched to "Test mode" for the purpose of carrying out the full function
test. Outputs of functions can be forced in this operating mode.
216
WARNING
WARNING
Hazardous Voltage.
Can Cause Death, Serious Injury, or Property Damage.
Testing the configuration on the MSS
Checking the printout alone is not sufficient; the configuration must be tested on the
MSS.
Result
The configuration is displayed. You are offline.
The "Prepare configuration test" dialog box opens.
The project printouts are generated. The project
switches to online mode.
System Manual, 10/2008, 926 2530-02 DS 02
Modular Safety System 3RK3

Advertisement

Table of Contents
loading

Table of Contents