Output Functions; Standard Output - Siemens Sirius 3RK3 System Manual

Modular safety system industrial switchgear monitoring and control devices
Hide thumbs Also See for Sirius 3RK3:
Table of Contents

Advertisement

Description of the software
6.7 Functions
6.7.11

Output functions

6.7.11.1

Standard output

Description
The function "Standard output" is required to switch the hardware outputs of the standard
output group.
Parameters
Parameter name
General
Parameters - Feedback
circuit
Parameters - Output
circuit
See also
Messages for output functions (Page 268)
204
Name
Element number
Element activated
Substitute value - Q1
Substitute value - Q2
Monitoring
Switching time [s]
Q1
Q2
Auxiliary outputs
AUX1
AUX2
FAULT
Description/parameter value
You can enter a name for the element here.
Consecutive number which is automatically assigned. You can
change the number.
When this parameter is active, the function is processed in the
safety logic.
When the parameter is deactivated, the set substitute value is
made available at the output Q.
"0" or "1" can be assigned to the substitute value when the
element is deactivated.
Substitute value "0" means output Q = 0
substitute value "1" means output Q = 1
-
-
-
Select the output for the processed signal.
-
Select whether auxiliary outputs are to be activated:
No
One auxiliary output
Two auxiliary outputs
Select the output for the processed signal. The auxiliary output
AUX1 supplies the same signal as Q. It can be switched with safe
or standard modules.
Only available when two auxiliary outputs are activated:
Select the output for the processed signal. The auxiliary output
AUX2 supplies the same signal as Q. It can be switched with safe
or standard modules.
-
Modular Safety System 3RK3